C. Refrigerant Loss

 

 

Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks, during and after 
manufacture. It is possible that shipping or other damage, or microscopic leaks over a long period, may 
result in the need for replenishment of refrigerant charge.

 

When it has been verified by a Certified EPA 

Technician that a refrigerant shortage does exist, the leak must be repaired. Then the unit may be 
evacuated and recharged in the field by a Certified EPA Technician only. 

 

 

CAUTION 

 

 
 

 
 
 
 

D.  Relocation

 

 

If your Kooltronic Air Conditioner has to be moved to another location by truck, the following precautions 
should be taken: 

I

De-mount Air Conditioner from equipment, controller or enclosure.

 

I

Conform to the applicable provisions of PROCEDURE FOR PROPER PACKING AND SHIPMENT 
OF KOOLTRONIC AIR CONDITIONERS in this manual under 

Section III. "PRODUCT HANDLING".

Refer to the data on the unit nameplate which specifies the type of 

refrigerant and the amount of charge in ounces. 

Before opening the Air Conditioner, disconnect all power.

.

IX. Trouble-Shooting 

 

Each Kooltronic Air Conditioner is engineered for performance and built for reliability. They are designed to 
require only routine maintenance. If your air conditioner should require warranty service, please contact 
Kooltronic. If you require service out of warranty, we have compiled a trouble-shooting chart to assist 
your service personnel. If additional assistance is required contact Kooltronic at (609) 466-3400

 

Problem

                                            Cause                                    Solution 

Unit does not run.

                                 No Power.                              Check Power Source and electrical connection.

                                                                                           Check unit ON-OFF switch (UL Listed units only).
                                                                                           Check unit power cord connection to terminal block.
                                                 

After initial 15 minute energization

       Return temperature is            Normal Operation. 

of air conditioner, compressor and

      between Thermostat set        Check return air temperature. 

condenser fan do not run.

                   point and differential              Check sensor connection on Thermostat. 

                                            (

75°F to 86°F). 

 

Unit not cooling. (Temperature

           Failed Thermostat                  Check Thermostat and Relay wire connections. 

difference between return and

             or Relay.                                 Replace Thermostat or Relay. 

supply air is less than 10°F).

                                                               

Evaporator Blower is running.                 Low Line Voltage.                   Check Nameplate Voltage against supply Voltage. 
Compressor and Condenser Blower                                                       
do not run. Return temperature is           Failed Compressor.                Check Compressor wire connections. 
above set point plus differential (90°F).                                                       Check Compressor overload. 

                                                                                           Check Compressor Capacitor. 
                                                                                           Replace Compressor. 

Summary of Contents for TRIMLINE KA4C2.0NP17L

Page 1: ...L BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com TRIMLINE KA4C2 0NP17L with Serial Numbers B17A0456 a...

Page 2: ...fic model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtu...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...ect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MO...

Page 5: ...bs the heat and is then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on t...

Page 6: ...re the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET p...

Page 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Page 8: ...te the factory setting is 75o F Refer to page 6 for instructions on adjustment of the thermostat 8 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or v...

Page 9: ...washers NOTE Make sure the press studs are inserted with heads toward you Tighten nuts securely 4 To facilitate easy mounting the three screws located on each side of the unit should be backed out en...

Page 10: ...102 4 1 12 28 6 0 75 19 0 M TAB MOUNTING PLAN 5 61 142 5 5 61 142 5 50 12 7 16 50 419 1 3 12 79 2 50 12 7 8 12 206 4 8 12 206 4 8 312 7 9 DIA HOLES 5 78 146 8 38 9 7 5 12 130 2 3 75 95 2 6 38 162 1 1...

Page 11: ...9 07 230 3 5 66 143 7 45 11 4 9 90 251 5 5 96 151 4 2 03 51 6 59 15 0 3 30 83 7 14 20 360 8 6 20 157 6 95 24 0 1 2 3 4 Drawings and Dimensions KA4C2 0NP17L Dimensions inches are for reference only and...

Page 12: ...Short Cycle Protector Filter Low Ambient Kit NEMA 12 Rating Maintained UL50 Programmable Temperature Alarm Programmable Thermostat UL CUL Listed Accessories and Options Filter Recoating Adhesive Inte...

Page 13: ...nd Service Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning CAUTION 1 Lift the filter using the attached tab to clear the lower filter retainer 2 A...

Page 14: ...erformance and built for reliability They are designed to require only routine maintenance If your air conditioner should require warranty service please contact Kooltronic If you require service out...

Page 15: ...r Clean Coil difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ice on Eva...

Page 16: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: