background image

8

VI. Pre-Installation Testing

 

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping 
integrity of the system. Please follow the steps below prior to installation. 

  

  

 

CAUTION 

 
 
 
 
 

 

1. The unit must sit in an upright position at a minimum room temperature of 65°F to allow the system to 

warm-up. This is particularly important during winter months. 

 2. Refer to the nameplate for proper electrical voltage and current requirements. Connect the power cord to 

a properly grounded and fused electrical supply, leaving electrical power to the unit turned off. 

 3. Note the factory thermostat setting which is 75

o

F.  

 4. Turn the electrical power on.  

 5. Verify that the evaporator blower or fan is running. 

 6. Verify that the condenser blower or fan is running.  

 7. Observe the temperatue on the digital display. The thermostat must be set at a minimum of 10

o

F below 

this temperature for the compressor to operate (the factory setting is 75

o

F). Refer to page 6 for 

instructions on adjustment of the thermostat. 

 8. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise or 

vibration should be evident. Both the evaporator and condenser fans or blowers should be delivering air 
through their respective discharge ports. The cool air discharged should be less than 70°F when the room 
temperature is between 70°F and 80°F. It is normal for the condenser blower to cycle on/off during this period.   

 9. Turn off the electrical power and disconnect the air conditioner from the power source.  

10. If any cover plug was removed to adjust the unit, be sure to replace it in order to maintain the integrity of 

the closed-loop airflow system.   

 

NOTE:

   Before shipment all Kooltronic Air Conditioners are subjected to a performance test. 

 

The air conditioner must be standing in its proper mounting position for a minimum of five 

(5) minutes prior to testing. Failure to follow this procedure will cause permanent damage to 

the compressor. To avoid compressor damage do not tip the unit more than 45° from its 

proper mounting position.

Summary of Contents for TRIMLINE KA4C2.0NP17L

Page 1: ...L BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com TRIMLINE KA4C2 0NP17L with Serial Numbers B17A0456 a...

Page 2: ...fic model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtu...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...ect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MO...

Page 5: ...bs the heat and is then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on t...

Page 6: ...re the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET p...

Page 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Page 8: ...te the factory setting is 75o F Refer to page 6 for instructions on adjustment of the thermostat 8 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or v...

Page 9: ...washers NOTE Make sure the press studs are inserted with heads toward you Tighten nuts securely 4 To facilitate easy mounting the three screws located on each side of the unit should be backed out en...

Page 10: ...102 4 1 12 28 6 0 75 19 0 M TAB MOUNTING PLAN 5 61 142 5 5 61 142 5 50 12 7 16 50 419 1 3 12 79 2 50 12 7 8 12 206 4 8 12 206 4 8 312 7 9 DIA HOLES 5 78 146 8 38 9 7 5 12 130 2 3 75 95 2 6 38 162 1 1...

Page 11: ...9 07 230 3 5 66 143 7 45 11 4 9 90 251 5 5 96 151 4 2 03 51 6 59 15 0 3 30 83 7 14 20 360 8 6 20 157 6 95 24 0 1 2 3 4 Drawings and Dimensions KA4C2 0NP17L Dimensions inches are for reference only and...

Page 12: ...Short Cycle Protector Filter Low Ambient Kit NEMA 12 Rating Maintained UL50 Programmable Temperature Alarm Programmable Thermostat UL CUL Listed Accessories and Options Filter Recoating Adhesive Inte...

Page 13: ...nd Service Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning CAUTION 1 Lift the filter using the attached tab to clear the lower filter retainer 2 A...

Page 14: ...erformance and built for reliability They are designed to require only routine maintenance If your air conditioner should require warranty service please contact Kooltronic If you require service out...

Page 15: ...r Clean Coil difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ice on Eva...

Page 16: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: