7
VII. Specific Model Data
Mounting
Kooltronic Air Conditioners have been engineered to be installed easily. To avoid damaging your Air
Conditioner, please read the following information before installation:
1. See Figure 1 for proper Mounting Template and Assembly Bracket (M/TAB) orientation. Place
M/TAB against the outside of the cabinet to locate cutouts and mounting holes.
Make sure the
cutouts don't interfere with components inside your cabinet.
2. Make the necessary cutouts and mounting holes in the cabinet. NOTE: Cutouts must not be
less than M/TAB openings.
3. Mount M/TAB to the outside of the cabinet using 6 sets of the mounting hardware supplied by
Kooltronic (1/4-20 press studs, nuts and washers). NOTE: Make sure the press studs are
inserted with heads toward you. Tighten nuts securely.
4. To facilitate easy mounting, the three screws located on each side of the unit should be backed
out enough to allow the M/TAB slot to fit.
5. Route the power cord through the top cutout in your cabinet. Line up the three screws on each
side of the unit with the slots on the M/TAB. Slide the unit inside the M/TAB.
6. Make sure there is a tight fit between the unit and M/TAB, before tightening the 10-32 self-
tapping screws. NOTE: Do not overtighten these screws.
7. Attach overflow drain hose supplied to the drain exit in the side of the unit. This hose must not
be elevated above the exit port. Improper mounting will impede the flow of condensate and
may cause internal malfunctions.
CAUTION
If the Air Conditioner is mounted to the cabinet door you must be sure
that the door hinges will support the additional weight of the Air
Conditioner. Also be certain that when the door is opened fully, the
cabinet does not become unbalanced. The actual weight of the unit can
be found in the performance specifications.
Dimensions (inches) are for reference only and are subject to change.
MOUNTING PLAN
(6)
1/
4
-20 WELD NUTS
WELD NUTS SUPPLIED FOR
ALTERNATE MOUNTING
METHOD TO MAINTAIN
NEMA 12. MOUNTING PLANS
FURNISHED ON REQUEST.
M/TAB
POWER
CORD
THERMOSTAT
ADJUSTMENT
ACCESS
FILTER
(8).312
[7.9] DIA.
HOLES
DRAIN
FILTERED
CONDENSER AIR INLET
(Ambient Air In)
CONDENSER OUTLET
(Warm Ambient Air Out)
WARM AIR RETURN
FROM ENCLOSURE
COOL AIR OUTLET
TO ENCLOSURE
1
2
3
4
3
4
2
3
4
1
12.13
[308.1]
17.50
[444.5]
9.00
[228.6]
12.25
[311.2]
.38
[9.7]
8.13
[206.5]
TYP.
5.75
[146.1]
.38
[9.7]
.88
[22.3]
6.38
[162.1]
4.13
[105.0]
17.50
[444.5]
5.00
[127.0]
.50
[12.7]
TYP.
.50
[12.7]
.38
[9.7]
12.25
[311.2]
11.25
[285.8]
6.13
[155.7]
11.25
[285.8]
3.13
[79.6]
FIGURE 1