IX. Trouble-Shooting 

 
Each Kooltronic Air Conditioner is engineered for performance and built for reliability. 
They are designed to require no routine maintenance other than the cleaning of ambient 
air filters. If your air conditioner should require service, we have compiled a 
trouble-shooting chart to assist your service personnel.  If additional assistance is 
required contact Kooltronic at 609 • 466-3400. 
 
 

Problem

                         Cause                                                Solution

 

Unit not Cooling                    No Power                                           Check Power Source and 

                                                                                    Electrical Connections 

                          Loss of Refrigerant                            Locate and repair leak 

                          Evaporator or Condenser                  Replace Motor, Capacitor or 
                          Blower not operating                         entire Assembly 

                          Filter clogged                                    Clean or replace Filter 

                          Clogged Evaporator or                      Clean Coil 
                          Condenser Coil 

                          Low Temperature Control                  Lower setting until unit starts 
                          (Thermostat) improperly set 

                          Low Temperature Control                  Replace Thermostat or Relay 
                          (Thermostat) defective                      when applicable 

                          Failed Compressor                            Replace Compressor 

Ice on Evaporator Coil          Insufficient Heat Load or Unit           Contact Kooltronic 

                          Oversized for Application 

                          Failed Evaporator Blower                  Replace Evaporator Blower 
                                                                                    Motor or Assembly 

                          Clogged Evaporator Coil                   Clean Coil 

Condensate draining             Enclosure not properly sealed          Check and seal all openings 
continuously 

                          Excessive opening of Enclosure       Eliminate the frequency of 
                                                                                    door opening 

Excessive vibration               Defective Motor in Blower                 Replace Motor 

                          Defective Wheel in Blower                Replace Wheel 

                          Compressor Loose                            Tighten Mounting Bolts 

Compressor Inoperative       Low line Voltage                                Check Nameplate Voltage 

                                                                                    against supply 

                          Loss of Compressor Oil                    Replace Compressor 

                          Loss of Refrigerant                            Locate and repair leak 

                          Failed Compressor Capacitor           Replace Capacitor 

                          Thermal Overload                             Contact Kooltronic 

                          Power interruptions                           Allow Compressor time to reset 

Refrigerant or Oil leaks         Crack or pin hole in tubing or            Replace tubing or rebraze joint 

                          brazed joint

Summary of Contents for TRIMLINE K2A4C1.0NP17L

Page 1: ...UAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com TRIMLINE NP17 SERIES with Serial Numbers up to M16...

Page 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...ect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MO...

Page 5: ...ure accumulated on the evaporator coil is collected in the condensate tray and released to the ambient air through the drain tube or the condensate evaporator The heat removed through the evaporator c...

Page 6: ...be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and co...

Page 7: ...tween the unit and M TAB before tightening the 10 32 self tapping screws NOTE Do not overtighten these screws 7 Attach overflow drain hose supplied to the drain exit in the side of the unit This hose...

Page 8: ...ent Air In CONDENSER OUTLET Warm Ambient Air Out WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE 12 13 308 1 6 1 4 20 WELD NUTS 2 1 3 4 12 25 311 2 9 00 228 6 17 50 444 5 2 1 3 4 Drawings...

Page 9: ...mensional changes Switchable Switch is internally mounted for security Rating shown is for operation at maximum ambient temperature 115V 60 Hz and 230V 60 Hz models also perform at full capacity when...

Page 10: ...nd the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic A...

Page 11: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Page 12: ...Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Ap...

Page 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...