VIII. Maintenance

 

 
Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air 
Conditioners are designed to require only the routine cleaning of air filters to assure 
unimpeded airflow through the condenser heat exchanger. It is not possible to 
recommend specific filter cleaning intervals since the level and the nature of airborne 
particulate matter differs widely with each installation. It is generally sufficient to remove 
and wash the reusable aluminum mesh air filters when the outer surfaces of these filters 
appear covered with a thin layer of dust or lint. Filter recoating adhesive is recommended. 
Appropriate disposable filters are available from Kooltronic. 
 
If filter service is neglected or delayed, the air conditioner will not perform at its design 
capacity. The first indication of excessively clogged air filters is usually a gradual 
increase of temperature within the equipment cabinet. If operation is continued under 
these conditions, the compressor will be shut off by the thermal overload device. The 
compressor will restart when its external temperature drops below the protector threshold 
setting and the compressor will continue to cycle on and off. Continued operation under 
these conditions will cause damage, shorten compressor life and void the warranty. 

 

A. Filter Removal and Service

 

 

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate 
necessary cleaning. 
 

CAUTION 

 
 

 

 
 
 
 

1) Lift the filter using the attached tab to clear the lower filter retainer. 
 
2) After removal, the filters should be flushed under warm running water with 

the clean side up, driving contaminants out the dirty side of the filter. If the 
accumulated dirt is oily, washing in a detergent bath is recommended, followed 
by a warm water rinse as above. 

 
3) The filters may be sprayed with 

Kooltronic A-16 Filter Recoating Adhesive

 to 

trap fine airborne contaminants, or they may simply be dried and reinstalled as 
strainer type filters. 

Recoating is recommended for best results. 

 
4) Reinstall the filter: (a) keeping the tab at the bottom, slide filter into the upper retainer, 

(b) press filter against the unit and, (c) slide down into lower retainer.

Do not operate the Air Conditioner for extended periods of time with the 

filter removed. The condenser coil may become clogged with dust or 

lint from the air entering the face. A clogged condenser coil is not 

readily detected and will give the same reaction as a clogged filter. A 

clean filter is the best protection.

Summary of Contents for TRIMLINE K2A4C1.0NP17L

Page 1: ...UAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com TRIMLINE NP17 SERIES with Serial Numbers up to M16...

Page 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...ect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MO...

Page 5: ...ure accumulated on the evaporator coil is collected in the condensate tray and released to the ambient air through the drain tube or the condensate evaporator The heat removed through the evaporator c...

Page 6: ...be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and co...

Page 7: ...tween the unit and M TAB before tightening the 10 32 self tapping screws NOTE Do not overtighten these screws 7 Attach overflow drain hose supplied to the drain exit in the side of the unit This hose...

Page 8: ...ent Air In CONDENSER OUTLET Warm Ambient Air Out WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE 12 13 308 1 6 1 4 20 WELD NUTS 2 1 3 4 12 25 311 2 9 00 228 6 17 50 444 5 2 1 3 4 Drawings...

Page 9: ...mensional changes Switchable Switch is internally mounted for security Rating shown is for operation at maximum ambient temperature 115V 60 Hz and 230V 60 Hz models also perform at full capacity when...

Page 10: ...nd the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic A...

Page 11: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Page 12: ...Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Ap...

Page 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...