background image

VII. Specific Model Data

Mounting

The Kooltronic Special Purpose Air Conditioners K_NA4C3P21R have been engineered to be installed easily.
These units utilize double layer gaskets. The first gasket layer is placed on the outside perimeter of the front panel
that is sealed against the customer enclosure. The second layer is placed on the two cutouts in the front panel.
The first gasket layer will allow a small amount of water between the two layers. The second gasket layer totally
protects an enclosure from ambient air, rain or hose down water. This gasket arrangement assures the integrity of
the closed loop system and is necessary to maintain the NEMA 4 rating.

Prior to mounting, refer to page 8 for the general arrangement drawing showing dimensions and locations of
mounting holes and cutouts. Prior to cutting or drilling, make sure that cutouts and mounting holes do not interfere
with components inside the cabinet. To avoid damaging your air conditioner, please read the following information
before installation:

CAUTION

7

If the air conditioner is mounted to the cabinet door you must be sure that the door hinges will

support the additional weight of the air conditioner. Also be certain that when the door is

opened fully, the cabinet does not become unbalanced. The actual weight of the unit can be

found in the performance specifications.

MOUNTING DRAWING

INSTALL THE MOUNTING PLATE W/STUDS 

    TO THE OUTSIDE WALL OF THE CUSTOMER'S 

 ENCLOSURE BEFORE INSTALLING A/C UNIT.

NOTE:

ENCLOSURE WALL

TYP. (3) PLACES

1/4'' NUT

  CUSTOMER'S 

ENCLOSURE

TYP. (3) PLACES

BOLT 1/4'' X 1-1/4''

RUBBER WASHER

         MOUNTING PLATE 

WITH STUDS

         TOP SECTION 

       OF A/C UNIT

         BOTTOM SECTION 

OF A/C UNIT

RUBBER WASHER

1/4'' NUT

1/4'' NUT

TIGHTEN NUT TO 

CLOSE GAP

1. It is recommended that a lift truck be used for installation.

2. Attach the Mounting Plate to the enclosure using (3)

1/

4

-inch

stainless steel nuts, (3) sealing washers as a spacer and (3)

1/

4

-

inch stainless steel mounting nuts. Sealing washers must be

placed against customer enclosure (see mounting drawing).

3. Place the air conditioner on the lift truck. Insert a 1-inch

(approximate) wooden block between the lift truck bottom and 
the air conditioner bottom so that the angle between the unit
mounting panel and the air conditioner is about 15 degrees.

4. Adjust the lift truck height so that the air conditioner hook is

located approximately 

1/

2

-

inch above the mounting plate.

5. Route the power cord through the discharge (upper) air cutout.

6. Move the air conditioner toward the enclosure panel so that the

gap between the hook and the enclosure is about .05-inch.

7. Slowly move the lift truck down until the hook engages with

the mounting plate. Continue to lower the lift truck. The air
conditioner will hang from the mounting plate flush against the
mounting panel.

8. Insert stainless steel screws through the holes in the mounting

plate bottom flange and the enclosure panel. Install sealing
washers and stainless steel nuts on each screw from inside the
enclosure and tighten (see mounting drawing).

Summary of Contents for K2NA4C3P21R

Page 1: ...UTION BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FA...

Page 2: ...ntroduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enc...

Page 3: ...a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating t...

Page 4: ...ESSURE P S I G LOW HIGH MAX FUSE SIZE SERVICE AIR FILTERS REGULARLY ALLOW 5 MIN BEFORE RESTARTING AFTER SHUTDOWN UNAUTHORIZED SERVICE OR MODIFICATION VIOLATES WARRANTY ALL MOTORS ARE THERMALLY PROTECT...

Page 5: ...leased to the ambient air by the condenser impeller The heat removed through the evaporator coil is transferred by the compressed refrigerant to the condenser coil Ambient air is then passed through t...

Page 6: ...test for proper operation This will verify the shipping integrity of the system Please follow the steps below prior to installation CAUTION 1 The unit must sit in an upright position at a minimum roo...

Page 7: ...O THE OUTSIDE WALL OF THE CUSTOMER S ENCLOSURE BEFORE INSTALLING A C UNIT NOTE ENCLOSURE WALL TYP 3 PLACES 1 4 NUT CUSTOMER S ENCLOSURE TYP 3 PLACES BOLT 1 4 X 1 1 4 RUBBER WASHER MOUNTING PLATE WITH...

Page 8: ...erence only and are subject to change 6 312 7 9 DIA HOLES 7 94 201 6 TYP 1 25 31 7 20 09 510 2 TYP 7 00 177 8 1 75 44 4 7 00 177 8 2 03 51 5 TYP 2 64 67 0 48 12 1 4 75 120 6 TYP 12 01 305 0 21 19 538...

Page 9: ...21R5 Part Part Number Part Number Part Number Compressor 0665 101 0665 107 0665 110 Compressor Impeller 0194 14 0194 15 0194 15 Condenser Impeller Capacitor 0452 06 0452 73 0452 73 Evaporator Fan 0265...

Page 10: ...RMAL CUTOUT T STAT 115 V 230 V TO CUSTOMER ALARM SYSTEM OPTIONAL TERMINAL BLOCK COOLING EFFECT DETECTOR BK T STAT SHORT CYCLE TIMER OPTIONAL SHORT CYCLE PROTECTOR OPTIONAL HEATER SPEED CONTROLLER COND...

Page 11: ...ld setting and the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service...

Page 12: ...e air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after manufacture It is...

Page 13: ...lay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blowe...

Page 14: ...14 This page intentionally left blank...

Page 15: ...is requested Original customer Purchase Order number and date Date product was received by customer Number of parts to be returned Product description model and serial number Reason for return Action...

Page 16: ...and a NEMA 3R interface with the enclosure Visit us online at www kooltronic com E Mail sales kooltronic com Integrity NEMA 4 4X Air Conditioners and Heat Exchangers Only by Kooltronic Designed for a...