The heater kit consists of a heater, a heat control thermostat and a heater limiter. The heater control
thermostat is a bimetal disk with a fixed set point of 60°F. When the entering evaporator air temperature rises
above 60°F the heater shuts off, and when the evaporator air temperature falls below 40°F the heater will
engage. The contact points of the alarm thermostat are normally closed. If the entering evaporator air
temperature exceeds 120°F the alarm thermostat contacts open, and when the temperature drops below
120°F the contacts close.

A condenser fan speed controller is standard on this unit. The speed controller temperature sensor is
installed in the airstream of the condenser. When the ambient temperature is above 95°F the condenser fan
will run at full speed. When the ambient temperature is between 85°F and 95°F the condenser fan will run
between maximum and minimum speed. When the ambient temperature is lower than 85°F the condenser
fan will cycle. In applications having frequent voluntary or involuntary power interruptions or heat load
fluctuations, a Compressor Short Cycle Protector is recommended to allow adequate time for the internal
pressure of the air conditioner to equalize before restarting.

When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75°F to
115°F enclosure temperature, depending on the ambient temperatures.

VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping
integrity of the system. Please follow the steps below prior to installation.

CAUTION

1

. The unit must sit in an upright position at a minimum room temperature of 65°F to allow the system

to warm-up. This is particularly important during winter months.

2. Refer to the identification label for proper electrical voltage and current requirements. Connect the

power cord to a properly grounded and fused electrical supply, leaving electrical power to the unit
turned off.

3. Note the factory thermostat setting which is 75

o

F.

4. Turn the electrical power on.

5. Verify that the evaporator blower or fan is running.

6. Verify that the condenser blower or fan is running.

7. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise

or vibration should be evident. Both the evaporator and condenser fans or blowers should be
delivering air through their respective discharge ports. The cool air discharged should be less than
70°F when the room temperature is between 70°F and 80°F.

8. Turn off the electrical power and disconnect the air conditioner from the power source.

9. If any cover plug was removed to adjust the unit, be sure to replace it in order to maintain the integrity

of the closed-loop airflow system.

NOTE:

Before shipment all Kooltronic Air Conditioners are subjected to a performance test.

6

The air conditioner must be standing in its proper mounting position for a minimum of five

(5) minutes prior to testing. Failure to follow this procedure will cause permanent damage to

the compressor. To avoid compressor damage do not tip the unit more than 45° from its

proper mounting position.

Summary of Contents for K2NA4C3P21R

Page 1: ...UTION BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FA...

Page 2: ...ntroduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enc...

Page 3: ...a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating t...

Page 4: ...ESSURE P S I G LOW HIGH MAX FUSE SIZE SERVICE AIR FILTERS REGULARLY ALLOW 5 MIN BEFORE RESTARTING AFTER SHUTDOWN UNAUTHORIZED SERVICE OR MODIFICATION VIOLATES WARRANTY ALL MOTORS ARE THERMALLY PROTECT...

Page 5: ...leased to the ambient air by the condenser impeller The heat removed through the evaporator coil is transferred by the compressed refrigerant to the condenser coil Ambient air is then passed through t...

Page 6: ...test for proper operation This will verify the shipping integrity of the system Please follow the steps below prior to installation CAUTION 1 The unit must sit in an upright position at a minimum roo...

Page 7: ...O THE OUTSIDE WALL OF THE CUSTOMER S ENCLOSURE BEFORE INSTALLING A C UNIT NOTE ENCLOSURE WALL TYP 3 PLACES 1 4 NUT CUSTOMER S ENCLOSURE TYP 3 PLACES BOLT 1 4 X 1 1 4 RUBBER WASHER MOUNTING PLATE WITH...

Page 8: ...erence only and are subject to change 6 312 7 9 DIA HOLES 7 94 201 6 TYP 1 25 31 7 20 09 510 2 TYP 7 00 177 8 1 75 44 4 7 00 177 8 2 03 51 5 TYP 2 64 67 0 48 12 1 4 75 120 6 TYP 12 01 305 0 21 19 538...

Page 9: ...21R5 Part Part Number Part Number Part Number Compressor 0665 101 0665 107 0665 110 Compressor Impeller 0194 14 0194 15 0194 15 Condenser Impeller Capacitor 0452 06 0452 73 0452 73 Evaporator Fan 0265...

Page 10: ...RMAL CUTOUT T STAT 115 V 230 V TO CUSTOMER ALARM SYSTEM OPTIONAL TERMINAL BLOCK COOLING EFFECT DETECTOR BK T STAT SHORT CYCLE TIMER OPTIONAL SHORT CYCLE PROTECTOR OPTIONAL HEATER SPEED CONTROLLER COND...

Page 11: ...ld setting and the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service...

Page 12: ...e air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after manufacture It is...

Page 13: ...lay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blowe...

Page 14: ...14 This page intentionally left blank...

Page 15: ...is requested Original customer Purchase Order number and date Date product was received by customer Number of parts to be returned Product description model and serial number Reason for return Action...

Page 16: ...and a NEMA 3R interface with the enclosure Visit us online at www kooltronic com E Mail sales kooltronic com Integrity NEMA 4 4X Air Conditioners and Heat Exchangers Only by Kooltronic Designed for a...

Reviews: