background image

10

VIII. Maintenance

Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air Conditioners are designed
to require only the routine cleaning of air filters to assure unimpeded airflow through the condenser
heat exchanger. It is not possible to recommend specific filter cleaning intervals since the level and the
nature of airborne particulate matter differs widely with each installation. It is generally sufficient to remove
and wash the reusable aluminum mesh air filters when the outer surfaces of these filters appear covered with
a thin layer of dust or lint. Filter recoating adhesive is recommended. Appropriate disposable filters are available
from Kooltronic.

If filter service is neglected or delayed, the air conditioner will not perform at its design capacity. The first
indication of excessively clogged air filters is usually a gradual increase of temperature within the
equipment cabinet. If operation is continued under these conditions, the compressor will be shut off by the
thermal overload device. The compressor will restart when its external temperature drops below the protector
threshold setting and the compressor will continue to cycle on and off. Continued operation under these
conditions will cause damage, shorten compressor life and void the warranty.

A. Filter Removal and Service

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning.

CAUTION

1) Remove the two screws from the rear panel.

2) Remove the rear panel from the unit.

3) Remove the filter from the filter holder by moving it up and towards you.

4) After removal the filter should be flushed under warm water with the clean side up, driving

contaminants out from the dirty side of the filter. If the accumulated dirt is oily, washing in a detergent
bath is recommended, followed by a warm water rinse as above.

5) The filter may be sprayed with Kooltronic A-16 Filter Coating Adhesive to trap fine airborne

contaminates, or it may simply be dried and reinstalled. Recoating is recommended for the best
results.

6) Reinstall the filter.

7) Replace the rear panel and attach it to the unit with two screws.

Do not operate the air conditioner for extended periods of time with the filter removed, as
the condenser coil may become clogged with dust or lint from the air entering the face. A

unit with a clogged condenser coil will have the same reaction as one with a clogged filter.

A clean filter is the best protection.

Summary of Contents for K2NA4C3P21L

Page 1: ...IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 42 INTEGRITY SERIES K_NA4C3P21L Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Page 2: ...el page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enclosures in capacities ranging from 1 000 to 30 000 BTU H Our closed loop design also ensures that your components will not be exposed to hot dirty operating condit...

Page 3: ...to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection to the correct power source Minimum circuit ampacity should be at least 125 of the amperage found on the air conditioner nameplate for the corresponding voltage Do not exceed the maximum fuse size found on ...

Page 4: ...correct type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRANTY UNAUTHORIZED SERVICE OR MODIFICATION OUTDOOR USE COMPARTMENT ONLY NEMA EEMAC UL50 BY UNDERWRITERS LABORATORIES INC TYPE 1 SPECIAL PURPOSE AIR CONDITI...

Page 5: ...moved through the evaporator coil is transferred by the compressed refrigerant to the condenser coil Ambient air is then passed through the condenser coil where it absorbs the heat and is then discharged to the environment This unit is equipped with a Low Temperature Thermostat to prevent the evaporator coil from freezing In conditions of low ambient temperature and low enclosure load the thermost...

Page 6: ...m temperature of 65 F to allow the system to warm up This is particularly important during winter months 2 Refer to the nameplate for proper electrical voltage and current requirements Connect the power cord to a properly grounded and fused electrical supply leaving electrical power to the unit turned off 3 Note the factory thermostat setting which is 75o F 4 Turn the electrical power on 5 Verify ...

Page 7: ...O THE OUTSIDE WALL OF THE CUSTOMER S ENCLOSURE BEFORE INSTALLING A C UNIT NOTE ENCLOSURE WALL TYP 3 PLACES 1 4 NUT CUSTOMER S ENCLOSURE TYP 3 PLACES BOLT 1 4 X 1 1 4 RUBBER WASHER MOUNTING PLATE WITH STUDS TOP SECTION OF A C UNIT BOTTOM SECTION OF A C UNIT RUBBER WASHER 1 4 NUT 1 4 NUT TIGHTEN NUT TO CLOSE GAP 1 It is recommended that a lift truck be used for installation 2 Attach the Mounting Pla...

Page 8: ...nd are subject to change 6 312 7 9 DIA HOLES 7 33 186 3 2 16 54 8 20 10 510 5 1 69 43 0 2 09 53 0 3 07 78 0 46 11 8 4 75 120 6 TYP 11 91 302 6 21 26 540 0 12 47 316 8 COOL AIR TO ENCLOSURE HEATED AIR FROM ENCLOSURE CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Heated Ambient Air Out 2 Places 7 91 200 9 6 91 175 5 6 75 171 4 1 25 31 6 TYP FIGURE 1 MOUNTING PLAN Dimensions inches metric are fo...

Page 9: ...NA4C3P21L K2NA4C3P21L5 Part Part Number Part Number Part Number Compressor 0665 101 0665 107 0665 110 Condenser Impeller 0194 14 0194 15 0194 15 Condenser Impeller Capacitor 0452 06 0452 73 0452 73 Evaporator Fan 0265 03 0265 06 0265 06 Filter 9501F 9501F 9501F Standard Features Condenser Impeller Speed Controller CFC Free refrigerant Filter Internal Corrosion Protection Low Temperature Control El...

Page 10: ...old setting and the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning CAUTION 1 Remove the two screws from the rear panel 2 Remove the rear panel from the unit 3 Remov...

Page 11: ...the air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after manufacture It is possible that shipping or other damage or microscopic leaks over a long period may result in the need for replenishment of refrigerant charge When it has been verified by a Certified EPA Technician...

Page 12: ...elay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Motor or Assembly Clogged Evaporator Coil Clean Coil Condensate draining Enclosure not properly sealed Check and seal all openings continuously Excessive opening of Enclos...

Page 13: ...inal customer Purchase Order number and date Date product was received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Air Conditioners must be returned in an upright positio...

Reviews: