VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping
integrity of the system. Please follow the steps below prior to installation.

CAUTION

1. The unit must sit in an upright position at a minimum room temperature of 65

o

F to allow the system to

warm up. This is particularly important during winter months.

2. Refer to the identification label for proper electrical voltage and current requirements. Connect the

power cord to a properly grounded and fused electrical supply, leaving electrical power to the unit
turned off.

3. Note the factory thermostat setting which is 75

o

F.

4. Turn the electrical power on. 

5. Verify that the evaporator blower or fan is running.

6. Condenser impeller should start immediately and after one (1) second, stop.

7. After three (3) to five (5) minutes the condenser impeller should start.

8. Verify that the condenser blower or fan is running.

9. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise or

vibration should be evident. Both the evaporator and condenser fans or blowers should be delivering
air through their respective discharge ports. The cool air discharged should be less than 70

o

F when the

room temperature is between 70

o

F and 80

o

F.   

10. If ambient temperature is below 75

o

F, after fifteen (15) minutes the thermostat will shut off the

compressor and the condenser impeller.

11. Turn off the electrical power and disconnect the air conditioner from the power source. 

12. If any cover plug was removed to adjust the unit, be sure to replace it in order to maintain the integrity

of the closed-loop airflow system.  

NOTE: Before shipment all Kooltronic Air Conditioners are subjected to a performance test.

The air conditioner must be standing in its proper mounting position for a minimum of five (5)

minutes prior to testing. Failure to follow this procedure will cause permanent damage to the

compressor. To avoid compressor damage do not tip the unit more than 45

o

from its proper

mounting position.

Summary of Contents for K2A6C10NPT47L

Page 1: ...IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 034 11 NPT SERIES K_A6...

Page 2: ...Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics en...

Page 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Page 4: ...ESSURE P S I G LOW HIGH MAX FUSE SIZE SERVICE AIR FILTERS REGULARLY ALLOW 5 MIN BEFORE RESTARTING AFTER SHUTDOWN UNAUTHORIZED SERVICE OR MODIFICATION VIOLATES WARRANTY ALL MOTORS ARE THERMALLY PROTECT...

Page 5: ...vaporator coil from freezing In conditions of low ambient temperature and low enclosure load the thermostat regulates the return air temperature from 75o F to 86o F The standard set point of the Low T...

Page 6: ...or fan is running 9 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and condenser fans or blowers sh...

Page 7: ...lets is essential for optimum performance of the air conditioner All externally mounted air conditioners are fully gasketed to ensure proper sealing This seal is necessary to maintain the integrity of...

Page 8: ...7 5 12 16 308 9 MOUNTING PLAN Dimensions inches mm are for reference only and are subject to change 2 06 52 3 17 4 3 2 60 66 0 2 1 1 2 4 3 J2 3 4 5 10 9 8 7 6 1 2 3 J1 CG RELAY CONTACTS N O 240 VAC 12...

Page 9: ...R SWITCH MOUNTING HOOKS 43 10 9 TYP 3 05 77 5 1 36 34 5 12 80 325 1 1 16 29 5 34 8 6 47 18 1198 4 33 65 854 7 7 80 198 1 12 22 310 4 8 54 216 9 50 12 7 DRAIN 8 71 221 2 1 31 33 3 12 02 305 3 1 89 48 0...

Page 10: ...L K2A6C13NPT47L Part Part Number Part Number Part Number Compressor 0665 407 0665 408 0665 412 Compressor Run Capacitor 0452 90 0452 32 0452 52 Condenser Blower Motor 0261 287 0261 288 0261 288 Conden...

Page 11: ...GN SUPPRESSOR T STAT 115 V 230 V OPTIONAL HEATER HEATER T STAT THERMAL CUTOUT CONDENSER BLOWER CAP CAP R C S O L COMPRESSOR OPTIONAL TERMINAL BLOCK COOLING EFFECT DETECTOR PRESSURE LIMITER PRESSURE SW...

Page 12: ...y A Filter and condenser coil service If an optional filter is installed on externally mounted air conditioners filter should not be used for internal mounted air conditioners the rear panel must be r...

Page 13: ...running Low Line Voltage Check Nameplate Voltage against supply Voltage Compressor and Condenser Blower do not run Return temperature is Failed Compressor Check Compressor wire connections above set p...

Page 14: ...r Clean Coil difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ice on Eva...

Page 15: ...iginal customer Purchase Order number and date Date product was received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Conta...

Page 16: ...effective solution for a variety of applications Available in a variety of sizes and airflows Models available with either NEMA 12 or NEMA 12 3R Ratings Advantage Sentry Series Fast convenient mounti...

Reviews: