V. Principles of Operation

Kooltronic Air Conditioners are required when the equipment
operating temperature must be kept near or lower than the
ambient room temperature, and/or the cabinet must be
sealed from dust, fumes, oil, corrosives and other
contaminants. These Air Conditioners utilize a "Closed-Loop
Cooling System" to ensure optimum performance of the
installed components.
Closed-Loop cooling seals the electronic enclosure from
hostile elements in the environment. Two separate
circulation systems are employed. The internal system cools
and dehumidifies the air inside the cabinet, totally isolating
the sensitive electronics and other components from the
environment. The external system uses circulating ambient
air or water to discharge the heat removed from the
electronics. The heat is dissipated from the enclosure by
means of the vapor compression refrigeration cycle. This
takes place in a hermetically-sealed refrigeration system,
utilizing either an air-cooled or water-cooled condenser heat
exchanger. The warm air inside the enclosure is drawn
through the evaporator coil where it is cooled, dehumidified
and returned.
Any enclosure moisture accumulated on the evaporator coil is collected in the condensate tray and
removed through the drain tube to the condensate evaporator. Condensate evaporates in the
condensate evaporator and is released to the ambient air by the condenser impeller. 
The heat removed through the evaporator coil is transferred by the compressed refrigerant to the
condenser coil. Ambient air is then passed through the condenser coil, where it absorbs the heat and
is then discharged to the environment.
This unit is equipped with a Low Temperature Thermostat to prevent the evaporator coil from freezing.
In conditions of low ambient temperature and low enclosure load, the thermostat regulates the
return air temperature from 75

o

F to 86

o

F. The standard set point of the Low Temperature Thermostat

is 75

o

F. The set point can be changed to 70

o

F or to 79

o

F by changing the location of the

thermostat jumper (See illustrations on page 8).
The Low Temperature Thermostat has a test start relay. When the air conditioner is turned on it will run
constantly for the first 15 minutes regardless of external temperatures. Afterwards, if the entering
evaporator air temperature is lower than the thermostat set point, the compressor and condenser
blower will stop, and the thermostat will begin to control the air conditioner.
The heater kit consists of a heater, a heat control thermostat and a heater limiter. The heater control
thermostat is a bimetal disk with a fixed set point of 60 F. When the entering evaporator air temperature
rises above 60

o

F the heater shuts off, and when the evaporator air temperature falls below 40

o

F the

heater will engage. The contact points of the alarm thermostat are normally closed. If the entering
evaporator air temperature exceeds 130

o

F the alarm thermostat contacts open, and when the

temperature drops below 130

o

F the contacts close. 

A condenser impeller controller is standard on this unit. When the ambient temperature falls below 70

o

F

the discharge pressure switch will cycle the condenser impeller. In applications having frequent
voluntary heat load fluctuations, an optional Short Cycle Protector is recommended. 
When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75

o

F to

115

o

F enclosure temperature, depending on the ambient temperatures.

COOL AIR TO
E

N

CLOSURE

 

HEATED AIR 
FROM 
E

N

CLOSURE

 

 CO

N

DE

N

SER

 
 (Heated Am

b

ient 

 

  OUTLET 

  Air O

u

t)

 

CO

N

DE

N

SER 

AIR I

N

LET 

(Am

b

ient Air In)

 

CO

N

DE

N

SER 

AIR I

N

LET 

(Am

b

ient Air In)

 

5

NPT47L

Summary of Contents for K2A6C10NPT47L

Page 1: ...IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 034 11 NPT SERIES K_A6...

Page 2: ...Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics en...

Page 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Page 4: ...ESSURE P S I G LOW HIGH MAX FUSE SIZE SERVICE AIR FILTERS REGULARLY ALLOW 5 MIN BEFORE RESTARTING AFTER SHUTDOWN UNAUTHORIZED SERVICE OR MODIFICATION VIOLATES WARRANTY ALL MOTORS ARE THERMALLY PROTECT...

Page 5: ...vaporator coil from freezing In conditions of low ambient temperature and low enclosure load the thermostat regulates the return air temperature from 75o F to 86o F The standard set point of the Low T...

Page 6: ...or fan is running 9 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and condenser fans or blowers sh...

Page 7: ...lets is essential for optimum performance of the air conditioner All externally mounted air conditioners are fully gasketed to ensure proper sealing This seal is necessary to maintain the integrity of...

Page 8: ...7 5 12 16 308 9 MOUNTING PLAN Dimensions inches mm are for reference only and are subject to change 2 06 52 3 17 4 3 2 60 66 0 2 1 1 2 4 3 J2 3 4 5 10 9 8 7 6 1 2 3 J1 CG RELAY CONTACTS N O 240 VAC 12...

Page 9: ...R SWITCH MOUNTING HOOKS 43 10 9 TYP 3 05 77 5 1 36 34 5 12 80 325 1 1 16 29 5 34 8 6 47 18 1198 4 33 65 854 7 7 80 198 1 12 22 310 4 8 54 216 9 50 12 7 DRAIN 8 71 221 2 1 31 33 3 12 02 305 3 1 89 48 0...

Page 10: ...L K2A6C13NPT47L Part Part Number Part Number Part Number Compressor 0665 407 0665 408 0665 412 Compressor Run Capacitor 0452 90 0452 32 0452 52 Condenser Blower Motor 0261 287 0261 288 0261 288 Conden...

Page 11: ...GN SUPPRESSOR T STAT 115 V 230 V OPTIONAL HEATER HEATER T STAT THERMAL CUTOUT CONDENSER BLOWER CAP CAP R C S O L COMPRESSOR OPTIONAL TERMINAL BLOCK COOLING EFFECT DETECTOR PRESSURE LIMITER PRESSURE SW...

Page 12: ...y A Filter and condenser coil service If an optional filter is installed on externally mounted air conditioners filter should not be used for internal mounted air conditioners the rear panel must be r...

Page 13: ...running Low Line Voltage Check Nameplate Voltage against supply Voltage Compressor and Condenser Blower do not run Return temperature is Failed Compressor Check Compressor wire connections above set p...

Page 14: ...r Clean Coil difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ice on Eva...

Page 15: ...iginal customer Purchase Order number and date Date product was received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Conta...

Page 16: ...effective solution for a variety of applications Available in a variety of sizes and airflows Models available with either NEMA 12 or NEMA 12 3R Ratings Advantage Sentry Series Fast convenient mounti...

Reviews: