background image

3

II. Incoming Inspection

Kooltronic Air Conditioners are designed, built and packaged to withstand the shock and vibration normally
associated with shipment by common carriers. Occasionally improper handling during shipping causes damage.
Such handling could include unbanding of palletized shipments, failing to respect 

"This Side Up"

arrows, rough

handling, falling off conveyors, excessive vibration, crushing, etc. Therefore, a thorough inspection should be done
upon receipt of all shipments. Any carton tears, dents, scratches, loose articles or evidence of oil are signs of
damage and should be noted on the Freight Bill. Cartons should be opened promptly and the units inspected for
CONCEALED DAMAGE. Kooltronic Air Conditioners must be delivered in the proper mounting position to assure
that damage to the compressor has not occurred during shipping. Any Kooltronic Air Conditioner that is delivered
removed from the banded pallet, lying down or double stacked should be refused.

An immediate claim MUST be filed with the freight carrier and an inspection requested. Retain all packing
materials. Kooltronic cannot assume responsibility for Consignee's failure to file a timely freight claim.

III. Product Handling:

1) Do not attempt to operate your Kooltronic Air Conditioner until you read and thoroughly understand this

Manual. See section

VI PRE-INSTALLATION TESTING.

2) Before operating the Kooltronic Air Conditioner be certain that it is placed in its correct mounting position.

This Air Conditioner is designed to operate in a vertical position only. 

This placement must be done a

minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump
area.

CAUTION

3) Before operating this unit, all electrical wiring must be checked to assure the proper connection to the

correct power source. Minimum circuit ampacity should be at least 125% of the amperage found on the
nameplate for the corresponding voltage. Do not exceed the maximum fuse size found on the nameplate.

4) We do not recommend that Air Conditioners be shipped to their final destination attached to an enclosure.

In the event that the Air Conditioner needs to be shipped attached to an enclosure it is strongly
recommended that proper support be provided for the Air Conditioner. Excessive vibration can occur if Air
Conditioners are not properly supported when shipped on enclosures, increasing the potential for internal
damage and voiding the warranty.

5)

PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR
CONDITIONERS:

Keep Air Conditioner in proper upright position indicated by arrow markers.

Pack Air Conditioner in an appropriate carton (preferably original carton if possible), with adequate
internal protective packaging, making sure carton is marked and is kept in correct upright position.

For local, controlled transportation, strap carton to a secure part of truck to prevent falling or
sliding, minimize vibration, etc.

For common carrier shipment, band unit(s) securely to a pallet. Unpalleted shipment risks
severe damage which voids the warranty.

Kooltronic Air Conditioners must be operated in their proper mounting position. If attempts are

made to operate a unit that is not in its designed mounting position, permanent compressor

damage will occur. This action will void the warranty. To avoid compressor damage do not tip the

unit more than 45° from its proper mounting position.

Summary of Contents for K2A4C2WNP28

Page 1: ...S IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com TRIMLINE WNP28 SERIES 900...

Page 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...Final Assy Number MFG Order Number e Before operating be sure that the power source matches these requirements y Use of incorrect type or amount of refrigerant will adversely affect performance and ma...

Page 5: ...ession refrigeration cycle This takes place in a hermetically sealed refrigeration system utilizing either an air cooled or water cooled condenser heat exchanger The warm air inside the enclosure is d...

Page 6: ...blower will be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evap...

Page 7: ...e top cut out in your cabinet Mount the unit to the M TAB by sliding the 4 studs on the side panel into the 4 slots on the M TAB After unit is in place tighten 2 screws at bottom of unit These two scr...

Page 8: ...ATER INLET 3 8 18 NPT MALE FITTING DRAIN 63 16 1 4 01 101 9 28 50 723 9 THERMOSTAT ADJUSTMENT 1 1 2 Drawings and Dimensions WNP28 SERIES Other drain outlets are available contact KOOLTRONIC Dimensions...

Page 9: ...ater temperature 115V 60 Hz and 230V 60 Hz models also perform at full capacity when operated at 100V 50 Hz or 200V 50 Hz respectively No transformer is required KA4C2WNP28 2000 1 0 115 100 60 50 13 0...

Page 10: ...nd the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic A...

Page 11: ...ypass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect...

Page 12: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Page 13: ...nal customer Purchase Order number and date Date product was received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact...