background image

6

VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the
shipping integrity of the system. Please follow the steps below prior to installation.

CAUTION

1. Allow the unit to sit in a upright position at a room temperature of 65°F minimum, allowing the

system to warm-up. This is particularly important in winter months.

2. Refer to the nameplate for proper electrical voltage and current requirements. Then connect the

power cord to a properly grounded and fused electrical supply. Leave the electrical power off.

3. Note the factory thermostat setting which is typically 75 to 80°F.

4

Adjust the thermostat to its maximum setting.

5. If the unit is equipped with an on-off switch, move it to the on position.  

6. Turn electrical power on.

7. Verify that the evaporator blower or fan is running.

8. Adjust the thermostat to its minimum setting. The compressor should start. On units equipped with

a short cycle protector, the compressor will have a delayed start of six (6) minutes from the time
the power is applied to the unit.  

9. Verify that the condenser blower or fan is running.  Note that on units equipped with a low ambient

kit, the start of the condenser fan or blower will be delayed until the system pressures rise.

10. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise

or vibration should be evident. Both the evaporator and condenser fans or blowers should be
delivering air through their respective discharge ports. The cool air discharged should be less than
70°F when the room temperature is between 70 and 80°F.  

11. On units equipped with heaters, adjust both the cooling and heating thermostats to their maximum

settings. Verify that the compressor and condenser fan or blower has stopped. Verify elevated
discharge air temperature from the evaporator air discharge.

12. If the unit is equipped with an on-off switch, leave it in the on position. Return the cooling

thermostat to its original setting. If the unit is equipped with a heater, return the heating thermostat
to its original position. 

13. Turn off the electrical power source, and disconnect the air conditioner from the power source.

14. If any cover plug is removed to adjust the unit, make certain to put it back in place to maintain the

integrity of the closed-loop airflow system.

NOTE:

Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a performance test.

The Air Conditioner must be standing in its proper mounting position for a

minimum of five (5) minutes prior to testing. Failure to follow this procedure

will cause permanent damage to the compressor.

Summary of Contents for K2A4C1.0MML

Page 1: ...RTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 036 00 Find additional info...

Page 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Page 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Page 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to th...

Page 5: ...ession refrigeration cycle This takes place in a hermetically sealed refrigeration system utilizing either an air cooled or water cooled condenser heat exchanger The warm air inside the enclosure is d...

Page 6: ...blower will be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evap...

Page 7: ...nditioner Also be certain that when the door is opened fully the cabinet does not become unbalanced The actual weight of the unit can be found on page 9 Mounting Narrow Mini 1 See Page 8 for proper Mo...

Page 8: ...363 4 15 87 403 0 15 93 404 6 10 62 269 7 POWER CORD FILTER DRAIN THERMOSTAT ADJUSTMENT ACCESS 1 4 00 101 6 1 50 38 1 8 00 203 2 4 50 114 3 1 00 25 4 1 00 25 4 4 50 114 3 4 31 109 4 2 75 69 8 81 20 5...

Page 9: ...7 1 58 KA4C2 0SML56 2000 115 50 115M 50 60 7 1 58 K2A4C2 0SML 2000 115 50 230 200 60 50 3 5 58 K2A4C2 0SML5 2000 115 50 230 50 3 2 58 Narrow Mini Series KA4C1 0NML 1000 125 50 115 100 60 50 7 1 53 KA4...

Page 10: ...ressor 0665 100 0665 102 0665 102 Condenser Blower Motor 0265 03 0261 08 0265 03 Condenser Blower Motor Capacitor N A 0452 03 N A Condenser Blower Assembly N A 7090 00 17 N A Evaporator Blower Motor 0...

Page 11: ...nd the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic A...

Page 12: ...ypass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect...

Page 13: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Page 14: ...ived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suit...

Reviews: