background image

9

Technical Data

RP33 Series

KA4C2RP33R

2000

125/115

0

115/100

60/50

13.6/13.3

98

K2A4C2RP33R

2000

125

0

230/200

60/50

5.8

98

KA4C3RP33R

3000

125/115

0

115/100

60/50

13.6/13.3

98

K2A4C3RP33R

3000

125

0

230/200

60/50

5.8

98

KA4C4RP33R

4000

125/115

0

115/100

60/50

13.6/13.3

98

K2A4C4RP33R

4000

125

0

230/200

60/50

5.8

98

KA4C5RP33R

5000

125/115

0

115/100

60/50

13.6/13.3

98

K2A3C5RP33R

5000

125

0

230/200

60/50

5.8

98

Ambient

Ambient

*

Approximate

BTU/H

Temp. °F

Temp. °F

Running

Weight

Model

Rating

Max.

Min.

Volts

Hz

Amps

(lbs.)

*

Rating shown is for operation at maximum ambient temperature.

115V, 60 Hz and 230V, 60 Hz models also operate at 100V, 50 Hz or 200V, 50 Hz respectively.  No transformer is required.

Major Component Replacements

KA4C_RP33R

K2A4C_RP33R

Part

Part Number

Part Number

Compressor

0665-101

0665-107

Compressor Capacitor

N/A

N/A

Condenser Blower Motor

0261-08

0261-54

Condenser Blower Motor Capacitor

0452-03

0452-03

Condenser Blower Assembly

200033-00-19

200033-00-58

Evaporator Blower Motor

0261-08

0261-54

Evaporator Blower Motor Capacitor

0452-03

0452-03

Evaporator Blower Assembly

5417-00-35

6008-00-10

Filter

7006F

7006F

NOTE: Part Numbers shown are for 60Hz/1Ø. For 50Hz consult Kooltronic.

Standard Features

Built-in Condensate Evaporator
CFC-Free Refrigerant
Crankcase Compressor Heater
Filter
Head Pressure Control Switch
Low Temperature Control Thermostat
NEMA 12 &  3R Ratings Maintained
UL/CUL Recognized

Summary of Contents for ADVANTAGE K2A3C5RP33R

Page 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com ADVANTAGE RP33 SERIES 900 039 32...

Page 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Page 3: ...operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection to the c...

Page 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Page 5: ...ied and returned Any enclosure moisture accumulated on the evaporator coil is collected and evaporated in the condensate evaporator tray and released to the ambient air by the condenser blower If late...

Page 6: ...a delayed start of 6 minutes from the time power is applied to the unit 8 Verify that the condenser blower or fan is running Note the start of the condenser fan or blower will be delayed until the sys...

Page 7: ...ut out in your cabinet Mount the unit to the M TAB by sliding the slots located on the front panel on the hooks of the M TAB 6 Tighten two screws on the bottom of the unit and seal the unit against th...

Page 8: ...4 1 56 39 6 2 68 68 2 6 18 156 9 1 00 25 4 DIA HOLE 12 35 313 6 10 45 265 4 8 59 218 2 10 94 277 9 12 35 313 7 Drawings and Dimensions RP33 SERIES 8 Dimensions inches mm are for reference only and are...

Page 9: ...odels also operate at 100V 50 Hz or 200V 50 Hz respectively No transformer is required Major Component Replacements KA4C_RP33R K2A4C_RP33R Part Part Number Part Number Compressor 0665 101 0665 107 Com...

Page 10: ...off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inle...

Page 11: ...mmended that the air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after ma...

Page 12: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Page 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: