VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping
integrity of the system. Please follow the steps below prior to installation.

CAUTION

1. Allow the unit to sit in a upright position at a room temperature of 65°F minimum, allowing the system

to warm-up. This is particularly important in winter months.

2. Refer to the nameplate for proper electrical voltage and current requirements. Then connect the power

cord to a properly grounded and fused electrical supply. Leave the electrical power off.

3. Note the factory thermostat setting is 75°F.

4. Heat up sensor bulb in evaporator compartment to 90°F using heat pipe or light bulb.

5. Turn electrical power on.

6. Verify that the evaporator blower or fan is running.

7. The compressor should start. On units equipped with a short cycle protector, the compressor will have a

delayed start of 6 minutes from the time power is applied to the unit.

8. Verify that the condenser blower or fan is running. Note, the start of the condenser fan or blower will be

delayed until the system pressures rise.

9. Operate the air conditioner for approximately ten minutes. During this period no unusual noise or vibration

should be evident. Both the evaporator and condenser fans or blowers should be delivering air through
their respective discharge ports. The cool air discharged should be less than 70°F when the room
temperature is between 70 and 80°F. 

10. Turn off the electrical power source, and disconnect the air conditioner from the power source.  

11. If any cover plug is removed to adjust the unit, make certain to put back in place to maintain the integrity

of the closed-loop airflow system.

NOTE:

Before shipment all Kooltronic, Inc. Air Conditioners are subjected to a performance test.

The Air Conditioner must be standing in its proper mounting position for a minimum of

five (5) minutes prior to testing. Failure to follow this procedure will cause permanent

damage to the compressor.

Summary of Contents for ADVANTAGE K2A3C5RP33R

Page 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com ADVANTAGE RP33 SERIES 900 039 32...

Page 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Page 3: ...operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection to the c...

Page 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Page 5: ...ied and returned Any enclosure moisture accumulated on the evaporator coil is collected and evaporated in the condensate evaporator tray and released to the ambient air by the condenser blower If late...

Page 6: ...a delayed start of 6 minutes from the time power is applied to the unit 8 Verify that the condenser blower or fan is running Note the start of the condenser fan or blower will be delayed until the sys...

Page 7: ...ut out in your cabinet Mount the unit to the M TAB by sliding the slots located on the front panel on the hooks of the M TAB 6 Tighten two screws on the bottom of the unit and seal the unit against th...

Page 8: ...4 1 56 39 6 2 68 68 2 6 18 156 9 1 00 25 4 DIA HOLE 12 35 313 6 10 45 265 4 8 59 218 2 10 94 277 9 12 35 313 7 Drawings and Dimensions RP33 SERIES 8 Dimensions inches mm are for reference only and are...

Page 9: ...odels also operate at 100V 50 Hz or 200V 50 Hz respectively No transformer is required Major Component Replacements KA4C_RP33R K2A4C_RP33R Part Part Number Part Number Compressor 0665 101 0665 107 Com...

Page 10: ...off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inle...

Page 11: ...mmended that the air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after ma...

Page 12: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Page 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: