76
Part Number STH063 9/17
Discharge Line Temperature Analysis
GENERAL
Knowing if the discharge line temperature is increasing,
decreasing or remaining constant can be an important
diagnostic tool. Maximum compressor discharge line
temperature on a normally operating ice machine steadily
increases throughout the freeze cycle. Comparing the
temperatures over several cycles will result in a consistent
maximum discharge line temperature.
Ambient air temperatures affect the maximum discharge
line temperature.
Higher ambient air temperatures at the condenser = higher
discharge line temperatures at the compressor.
Lower ambient air temperatures at the condenser = lower
discharge line temperatures at the compressor.
Regardless of ambient temperature, the freeze cycle
discharge line temperature will be higher than 150°F (66°C)
on a normally operating ice machine.
PROCEDURE
Connect a temperature probe on the compressor discharge
line within 6" (15 cm) of the compressor. Observe the
discharge line temperature for the last three minutes of
the freeze cycle and record the maximum discharge line
temperature.
Summary of Contents for KDT0300A
Page 1: ...Part Number STH063 9 17 Koolaire KT Model Ice Machines Technician s Handbook ...
Page 2: ......
Page 26: ...26 Part Number STH063 9 17 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 Part Number STH063 9 17 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 114: ...114 Part Number STH063 9 17 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 150: ...150 Part Number STH063 9 17 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 151: ......