6.3.  Condenser coil 

Reference to 

Maintenance Schedule Bus

 No.: WP 07 05 06 18

The condenser coil fins have to be cleaned with compressed air at least once a year, in case of se-
vere soiling more often

.

 

 

Attention

Always  keep  condenser coil  fins  clean.  Severe  soiling  cause’s  excess  pressure  within  the  a/c-unit 

system and it automatically stops working. 

6.4.  Troubleshooting 

   

Only qualified staff is allowed to

 

carry out these works! - 

Trouble 

Cause 

Repair    

only by refrigeration expert 

 

A/c is not running 
 

magnetic clutch is not switched on 

  check inside temperature, adjust new 

if necessary   

  check connections at magnetic clutch 

electrical connections disconnected 

  check electric connections at switch-

board 

relay defective 

  check relay, replace if necessary 

defrost thermostat has switched off 

  check evaporator blower, replace if 

necessary 

outside temperature too low (possible 
icing of evaporator) 

  switch on "ventilation" only

 

2

 

evaporator coil dirty 

  clean evaporator coil with compressed 

air 

compressor does not compress 

  check  high and low pressure, replace 

compressor if necessary 

 
excess pressure (pressure too high) 

  check axial fans 

  check fuses at switchboard 

  clean condenser coil with compressed 

air 

excess pressure caused by high out-
side temperature 

  run unit until pressure has stabilized

 

2

 

leakage in a/c unit, lack of refrigerant 

  check a/c unit for leakages 

  refill

 

refrigerant 

low pressure, dryer clogged 

  replace dryer 

screen of expansion valve clogged 

  clean screen; replace dryer 

Loud noise at 
compressor 

defective bearing at compressor 

  replace either bearing or entire com-

pressor 

slack V-belt 

  check V-belt at compressor drive 

1

 

On our website www.konvekta.com in category >service< you will find a survey of contact details of all our 
service partners close to your location. 

2

 

By user 

Summary of Contents for KL30

Page 1: ...t Germany 49 0 66 91 76 0 49 0 66 91 76 200 Info konvekta com www konvekta com Operating Instruction for KONVEKTA Air Conditioning unit KL30 KL30T with control KS50 Versions 12 respectively 24 Volt DC Fresh Air Heating ID BBA KL30T12AD Version A02 ...

Page 2: ...ning unit 8 5 3 Switch off air conditioning unit 8 5 4 Setting of the desired temperature 8 5 5 Manual adjustment of the blowers 9 5 6 ECON operation 9 5 7 Fresh and recirculating air operation 10 5 8 Demisting operation 10 5 9 Changeover temperature display mode 11 5 10 Switch the temperature indication to Fahrenheit 12 6 Maintenance Service 12 6 1 Compressor 12 6 2 Return air grid 12 6 3 Condens...

Page 3: ...increases operation reliability and service life of the air condi tioning unit and reduces life cycle costs Please complete these instructions by adding the national provisions for prevention of accidents and environmental protection These instructions are part of the air conditioning unit Always have a copy at hand in the driver s cabin You will certainly understand that we will not recognize any...

Page 4: ...se your product is equipped with details not shown or described in the operating in struction your KONVEKTA Service Station will always be at disposal for informing you about correct operation In the course of further developments we reserve the right to technical modifications without notice Guarantee and liability conditions of KONVEKTA AG s general business conditions are not enlarged by the ab...

Page 5: ...aft seal of the compressor The compressor should be started every 4 weeks for approx 15 minutes This also applies when the vehicle is not into operation for a longer period or when the air condition ing unit is not used Compressor Type SD7H15 Weight kg approx 7 5 Oil brand quantity liter PAG depend ing on version3 Magnetic clutch 2 24V DC Attention for SD7H15 Only clockwise rotation 1 Weight witho...

Page 6: ...NOTE KONVEKTA uses components made of copper and aluminium which last a whole unit life time under normal environmental conditions Should the units be operated under aggressive envi ronmental conditions i e air containing salt phosphate or ammoniac extremely a corrosion of the cupper and aluminium components can not be ruled out The cupper and aluminium components of the KONVEKTA systems are not s...

Page 7: ...Please note that the control panel keys have not been designed for heavy stressing Excessive or fast pressing of the keys for adjusting the set temperature does not accelerate the cooling down process It possibly damages the control panel and so affects the general perfor mance of the air conditioning unit 5 1 Description of the display LCD symbols Symbol Acceptation of the display symbols 1 Ambie...

Page 8: ...ars here 20286 hours Now the A C is ready for operation The last stored setting is displayed 5 3 Switch off air conditioning unit By pressing the key Blowers Minus 2 longer than 2 seconds the A C is switched off While the key is pressed the display changes temporarily This is no fault no settings are changed Press and hold Now the A C is switched off 5 4 Setting of the desired temperature The set ...

Page 9: ... 11 indicates that the unit is in cooling mode at the moment The ECON mode can be activated by pressing and holding key Set Tempera ture Minus 7 While the key is pressed the display changes temporarily This is no fault no settings are changed Press and hold Now the ECON mode is activated and the ECON symbol 12 is displayed In ECON mode the compressor is locked The A C operates only in ventilation ...

Page 10: ...5 8 Demisting operation If the windows are steamed up the demisting mode can be activated Press key Demisting 4 to activate demisting operation mode Press The symbol Demisting 10 on the display indicates that the demisting mode is activated In demisting mode the compressor is operating and the blower speed is raised to 100 If the key Demisting 4 is pressed again the demisting mode gets deactivat e...

Page 11: ...mbol Inside Temperature 2 appears By pressing key MODE 6 once again the display changes over to set tem perature indication Press The set temperature is displayed When the demisting mode is activated the blower speed is increased to 100 The speed can be adjusted manually on demand But to reach maximum demisting performance the blower speed should not be decreased If the set temperature is adjusted...

Page 12: ...nd maintenance works please contact via email TKD konvekta com Danger of accidents Qualified staff in charge of installation and maintenance have to be trained in accordance with EN 378 Part 4 and EC No 307 2008 and must strictly follow the legal provisions Any works or modifications at the air conditioner which are carried out improperly can lead to mal function and so endanger operational reliab...

Page 13: ...as switched off check evaporator blower replace if necessary outside temperature too low possible icing of evaporator switch on ventilation only 2 evaporator coil dirty clean evaporator coil with compressed air compressor does not compress check high and low pressure replace compressor if necessary excess pressure pressure too high check axial fans check fuses at switchboard clean condenser coil w...

Page 14: ...lance Resolution for the waste management of old cars and the adaptation of road prescriptions Resolution EC No 2037 2000 of the Euro pean Parliament and of the Council for ma terials that affect the ozone layer Resolution to prohibit certain ozone destroy ing halogen hydrocarbons The used refrigerant endangers the environment When dealing with refrigerants the existing pre scriptions and regulati...

Reviews: