31
KON-215-60-33.2-v.1.0-E
RFD TEHNICAL DESCRIPTION.doc
RECORDS AND EVENT LOGS
Event records and disturbance logging
Event log
Log of all events
500
Trip log
Log of all events related to trip
500
Disturbance log
log of disturbance recordings
2kHz
1kHz
12s / 8
24s / 8
Reset Event log
Delete event log
password
Reset Trip log
Delete trip log
password
Reset Disturbance log
Delete disturbance log
password
SISTEMSKI PARAMETRI
Measurement transformers ratios
- rated primary current on side A
CTA prim
1
– 2000 A
default: 100 A
- rated secondary current on side A
CTA sec
1 A
5 A
default: 1 A
- rated primary current on side B
CTB prim
1
– 2000 A
default: 100 A
- rated secondary current on side B
CTB sec
1 A
5 A
default: 1 A
- rated primary current Io on side A
CToA prim
1
– 2000 A
default: 100 A
- rated secondary current Io on side A
CToA sec
1 A
5 A
default: 1 A
- rated primary current Io on side B
CToB prim
1
– 2000 A
default: 100 A
- rated secondary current Io on side B
CToB sec
1 A
5 A
default: 1 A
- measurement transformer grounding on side A
CTA Starpoint
Transformer
Busbar
default: Transformer
- measurement transformer grounding on side B
CTB Starpoint
Transformer
Busbar
default: Transformer
- ground current measurement transformer grounding on side
A
CToA Starpoint
Transformer
Ground
default: Transformer
- ground current measurement transformer grounding on side
B
CToB Starpoint
Transformer
Ground
default: Transformer