After selecting program for each day of the week “1-7” schedule setting window is introduced:
Each day of the week has 3 events: N1, N2, N3. Settings start from Monday (Mo). When the event of the day is
selected, event start and end time is set and ventilation intensity level (0, 1, 2, 3) is assigned.
Before selecting work days and weekend operation mode schedule “1-5/6,7” menu window is introduced:
After event (N1, N2, N3) is selected for work days “1-5”, each event start and end time and ventilation intensity is
set the same way. The same way three unit operating events are set for the weekend:
Note:
Every event start and end time is set from 0:00 to 23:59 h.
For instance:
Monday:
N1 from 00:00 to 07:00 2 ventilation level
N2 from 10:00 to 20:00 1 ventilation level
N3 from 20:00 to 23:59 3 ventilation level
12. Language setting
Language selection menu has been projected on the control panel. To set language the last menu window should
be selected:
13. Menu locking
The PIN code is provided to lock entering to the parameters setting menu. If the menu is locked, only main para-
meters can be reviewed also the unit may be switched on or off.
To enter the PIN code, touch
+
and hold for 4 seconds till corresponding window appears:
To enter the PIN code follow these steps:
1. Touch
or
to enter the first digit.
2. Touch
to go to the second digit.
3. Repeat the steps above to enter the second and the third digits.
4. After third digit is entered touch
to confirm the code.
5. Touch
and
and hold for 4 seconds to save the code into controller memory.
The menu can be unlocked only with the PIN code. If the code is forgotten,
contact local service team.
7.7. Other Control Functions
1. Remote unit control
Unit is provided with remote control possibility using external device (button, timer, other sensor), which is connected
to the contacts 17, 18 (see chapter 6.3c Picture) or 27, 28 (see chapter 6.3 d Picture).
This function can perform one of two operations:
•
remote unit switching on and off;
•
remote unit intensity control (additional ordered function).