“Over load” LED flashes when total current exceeds the rated one. 

Load Protection activated 60 seconds after the current is 1.2 times more than rate one. 

Load Protection activated at once when the current 1.5 times more than rate one. 

        When protection activated, all the loads will be disconnected, then “Over load” LED stops 

flashing but keeps on. 

After the malfunction removed, press any button to return to work. 

 

5

Operation Instructions 

LCD, 4 buttons, 6 LEDs are fixed on KC3. 

1). Working Status, all the working data shown on the LCD 

2). Setting Status, adjust the data shown on the LCD. 

Working Status is the default mode when electrified 

 

Data on LCD under Working Status

 

All the data: Working Mode, Switch Status, Input DC Voltage of Solar Modules, Input DC Current 

of Solar Modules, Input Power of Solar Modules, Battery Voltage, Loads Current, Current Time, 

Battery Temperature, are all shown on LCD, moving in cycles. 

 

Table 1. Data on LCD under Working Status 

No Display 

Meaning 

Unit

Format  Remark 

1 “MODE+STATUS” 

Working Mode and   

Switch Status of load 

 

 

4 modes & 2 status 

Vpv 

Input Voltage of Solar Modules 

XX.X 

 

Ipv 

Input Current of Solar Modules

XX.X 

 

Ppv 

Input Power of Solar Modules 

XXX 

 

5 Vbat 

Battery 

Voltage  V 

XX.X 

 

Iw 

Loads Current 

XX.X 

Current of total loads

Pw 

Loads Power 

XX 

Power of total loads 

8 Tbat 

Battery 

Temperature 

 XX 

 

9 TIME 

Current 

Time 

 

HH:MM:SS   

 
 
 
 
 
 

                       

                        Diagram 3      First roll (page) shown on LCD 

1. LD

...

PV

..

OFF 

2. Vpv

..

...

..

XX.X 

3. Ipv

..

...

..

 XX.X 

4. Ppv

..

...

..

XXX

 

Summary of Contents for KC3

Page 1: ...ts under different working conditions 1 6 Protection for Batteries Overcharge Overdischarge Low volt Protection for Overload Short Circuit Protection for Reverse Polarity of solar modules Protection f...

Page 2: ...de of batteries anode of loads cathode of loads Cables Selections according to Current of Loads Selected cables to connect batteries are better shorter thicker to prevent power loss Note KC3 is design...

Page 3: ...agement 4 Control modes are optional Time shall be reset when controller re connected with power Light Switch Mode Default Mode Under this mode it will activate voltage when Light gets lower to the se...

Page 4: ...s from Initial Impact Current Efficient PWM begins to charge after a certain charge from the battery and turns to Voltage Limit Charge when goes into the limited line Float Charge begins and keeps its...

Page 5: ...high charging voltage Overdischarge Low volt Protection Low volt flashes when the batteries voltage is too low it will stop flashing to turn to red if voltage keeps down to the Protection Line and lo...

Page 6: ...fault mode when electrified Data on LCD under Working Status All the data Working Mode Switch Status Input DC Voltage of Solar Modules Input DC Current of Solar Modules Input Power of Solar Modules Ba...

Page 7: ...TIME Current Time HH MM SS 00 00 0 0 hour minute second For time checking 2 Ibat max Maximum Battery charging current A XX X 40 0 Set within 5 0A 40 0A 3 Vbat max Allowed Maximum Battery Charging Curr...

Page 8: ...to pause charging when battery voltage exceeds to this set voltage Re charging starts at a low current when the battery voltage is back to charging voltage 4 No 4 is set to disconnect the load when th...

Page 9: ...ormal status 4 buttons on KC3 setting button next up increase down reduce setting button Under normal status when LCD shows the working status press and hold 5 seconds setting button to enter the sett...

Page 10: ...he cursor is located on working mode selection press up increase 4 modes will be shown orderly as PV PV TIME TIME MANUAL Under normal status press down reduce LCD turns over to next page When KC3 unde...

Page 11: ...to required one Sunlight works but voltage of solar module indicates 0 Check the connection of the modules and make sure right connection for and Over volt turns on no output Check the connection of...

Page 12: ...when the current 1 5 times more than rate one Low voltage alarm 11 4V 22 8V Overdischarge Low volt protection voltage 10 8V 21 6V Overdischarge Low volt recovery voltage 13 4V 26 8V Over voltage alar...

Reviews: