FUTURE® S AIR HANDLING UNIT
OPERATION AND MAINTENANCE
INSTRUCTIONS
15 December 2020
Ver 1.7 (We reserve the right to changes without prior notice)
5
WARNING
Electrical connections must be made by a qualified and authorised electrician only. The
condition of the cables connected to the unit must be inspected visually before making any
electrical connections and starting the unit. Before starting any installation and
maintenance work on the electrical device, make absolutely sure that the device is de-
energised. After switching off the power, wait at least five minutes to allow dangerous
voltages to discharge from the devices. Electrical devices should be inspected every six
months. Any deficiencies and faults must be rectified immediately.
WARNING
Due to functional reasons, fans/motors may start and stop automatically without warning.
This may happen, for example, after a power outage or malfunction.
WARNING
Do not use components other than those specified or approved by the equipment
manufacturer in the ventilation unit.
CAUTION
The unit must be installed in a space accessible only to qualified personnel. If the unit is
installed in a place where it is accessible to persons other than service personnel, the
handles of the access doors must be removed and locked in a safe place. Ensure during
installation, commissioning and maintenance that only qualified maintenance personnel
have access to the danger area.
CAUTION
The ventilation system and its maintenance routes must be designed and constructed so
that the ventilation unit can be serviced and repaired easily and safely. The National
Building Code of Finland 1009/2017, Section 24 of the Ministry of the Environment Decree
on the indoor climate and ventilation of buildings
CAUTION
The filters’ pressure difference values must under no circumstances exceed the
dimensioning pressure drop in the filters by more than two times. If the pressure difference
is exceeded, the components or structure of the unit may become damaged. The warranty
does not cover damages due to negligence in replacing the filters
CAUTION
If the unit is equipped with drainages for washing water, these must be plugged. If the
drainages are sewered, they must be equipped with a water trap.