2.4

Risks relating to exhaust gases

 DANGER

RISK OF POISONING
DANGER OF DEATH (if appropriate)

The  carbon  monoxide  present  in  the  exhaust  gas  may  lead  to  death  by  inhalation  if  the 
concentration levels in the atmosphere are too high.
Always use the unit in a well ventilated area where the gases cannot accumulate.

For safety reasons and for correct operation of the unit, correct ventilation is essential (risk of poisoning, engine overheating and 
accidents involving, or damage to, the surrounding equipment and property). If it is necessary to operate it inside a building, the 
exhaust gases must be evacuated outside and adequate ventilation must be provided so that any people or animals present are not 
affected.

2.5

Risk of fire

 DANGER

RISK OF FIRE
DANGER OF DEATH

Never  operate  the  unit  in  areas  containing  flammable  products  (risk  of  sparks).  Keep  all 
flammable  or  explosive  materials  (e.g.  petrol,  oil,  cloth,  etc.)  out  of  the  way  when  unit  is 
running. Never cover the unit with any type of material while it is in operation or just after it has 
been turned off: always wait until the engine cools down (at least 30 minutes).

2.6

Risk of burns

IMPORTANT

Before any intervention, wait for the unit to cool down (at least 30 minutes).

When running and just after stopping, the oil, engine and the exhaust silencer are hot and may cause burns if contact is made.

2.7

Risk of electrocution

 DANGER

RISK OF ELECTROCUTION
DANGER OF DEATH

Units supply electrical current while operating; comply with the applicable legislation as well as 
the  installation  and  usage  recommendations  given  in  this  manual.  If  you  are  in  any  doubt 
regarding installation, please contact your nearest agent.
Do not connect the unit directly to other power sources (such as the mains for example); fit a 
source changeover panel.
Never touch stripped cables or disconnected connectors. Never handle a unit with wet hands 
or feet. Never expose the equipment to liquid splashes or rainfall, and do not place it on wet 
ground.

2.7.1 Installation temporaire ou semi-permanente (chantier, spectacle, activité...)

A - If the unit is not equipped with an integrated differential protection device at delivery (standard version with insulated neutral on 

the unit's earth terminal):
- Use a differential device calibrated to 30mA at the output of each of the unit's sockets (place each device at least 1 metre from 

the unit, protecting it from weather conditions).

- If one or more mobile or portable devices are used occasionally, the unit does not need to be earthed.

B  -  If  the  unit  is  equipped  with  an  integrated  differential  protection  device  at  delivery  (standard  version  with  alternating  neutral 

connected to the unit's earth terminal - for use with TT or TN systems):
- Connect the unit to the earth: attach a 10 mm2 copper wire to the unit's earth terminal (A1) and to a galvanised steel earthing 

rod set 1 metre into the ground.

2.7.2 Fixed installation or mains failure

When  supplying  a  fixed  installation  (e.g.  as  backup  for  mains  outages),  the  unit  must  be  connected  by  a  qualified  electrician  in 
accordance  with  the  regulations  applicable  at  the  installation  site.  The  units  are  not  designed  to  be  connected  directly  to  an 
installation (risk of electrocution or damage to equipment).
A - If the unit is not equipped with an integrated differential protection device at delivery (standard version with insulated neutral on 

the unit's earth terminal): 

- Use a source inverter.
- The unit does not need to be earthed.

B  -  If  the  unit  is  equipped  with  an  integrated  differential  protection  device  at  delivery  (standard  version  with  alternating  neutral 

connected to the unit's earth terminal - for use with TT or TN systems):

- Use a source inverter.
- Connect  the  unit  to  the  earth:  attach  a  10 mm2  copper  wire  to  the  unit's  earth  terminal  (A1)  and  to  a  galvanised  steel 

earthing rod set 1 metre into the ground.

2.7.3 Mobile application

The units are intended to operate while stationary. They may not be installed on a vehicle or other mobile equipment unless a study 
has been carried out analysing the unit's various installation and usage specifications. It is prohibited to use the unit whilst it is in 
motion. If earthing is not possible, connect the unit's earth terminal (A1) to the vehicle earth.

14/24

Summary of Contents for SDMO Technic 6500 A AVR UK C5

Page 1: ...33522200401_2_1 11 2019 Manuel d utilisation et d entretien Notice originale Instruction and maintenance manual Translation of the original note TECHNIC 6500 A AVR UK C5...

Page 2: ...A 1 3 14 7 18 6 16 17 5 4 10 6 9 8 13 23 12 12 20 21 19 19 11 22 15 24 2 25 26...

Page 3: ...B C 3 1 2 4 5 2 5 1 4 8 7 6 3...

Page 4: ...D E F FRANCE 0 806 800 107 Prix appel 5 1 2 6 3 4 1 3 2 2 1...

Page 5: ...on des personnes Les consignes et r gles de s curit sont lire attentivement et respecter imp rativement pour ne pas mettre en danger la vie ou la sant des personnes En cas de doute sur la compr hensio...

Page 6: ...ler un appareil les mains ou les pieds humides Ne jamais exposer le mat riel des projections de liquide ou aux intemp ries ni le poser sur un sol mouill 2 7 1 Installation temporaire ou semi permanent...

Page 7: ...ition DANGER RISQUE DE PERTE D AUDITION Lors du fonctionnement de l appareil porter imp rativement des protections auditives adapt es 2 9 Risques lors des op rations de manutention d utilisation et d...

Page 8: ...du mat riel et la totalit de la commande 2 Si l appareil est muni d une bride de transport la retirer La bride de transport est une plaque m tallique situ e sous le moteur pr s de la borne de mise la...

Page 9: ...ifier visuellement le niveau de carburant sur l indicateur A5 la palette rouge de l indicateur doit se situer entre le niveau maximum de carburant F Full plein et le niveau minimum de carburant E Empt...

Page 10: ...s conditions d utilisation de l appareil et des besoins Effectuer les entretiens aux ch ances calendaires indiqu es m me si le nombre d heures de fonctionnement n est pas atteint La garantie est notam...

Page 11: ...uvercle du filtre air et le verrouiller 5 3 5 Nettoyer le pare tincelles 1 Sur le silencieux d chappement d visser la vis de fixation du pare tincelles E2 2 D poser le pare tincelles A25 E1 3 A l aide...

Page 12: ...moteur neuve 7 Remettre en place une bougie d allumage neuve 8 Tirer plusieurs fois la poign e du lanceur r enrouleur A24 pour r partir l huile dans le cylindre Remiser l appareil 9 Nettoyer l appare...

Page 13: ...er Bluetooth GSC101 lorsque l alerte s affiche dans l application Generator Smart Care environ tous les deux ans 1 A l aide d un petit tournevis cruciforme ouvrir le couvercle du bo tier 2 Retirer les...

Page 14: ...rr te automatiquement le moteur pour pr venir tout endommagement Dans ce cas v rifier le niveau d huile moteur et faire l appoint si n cessaire avant de proc der la recherche d une autre cause de pann...

Page 15: ...e nombre d heure de fonctionnement prendre en compte est de 8 heures par jour CONDITIONS D APPLICATION DE LA GARANTIE La garantie d bute compter de la date d achat de l appareil par le premier utilisa...

Page 16: ...tre appareil durant les 6 mois suivant la d livrance du bien Ce d lai est port 24 mois compter du 18 mars 2016 sauf pour les biens d occasion La garantie l gale de conformit s applique ind pendamment...

Page 17: ...aterial damage 2 Instructions and safety regulations personal protection The instructions and safety regulations must be read carefully and followed to avoid endangering personal health and safety If...

Page 18: ...e ou semi permanente chantier spectacle activit A If the unit is not equipped with an integrated differential protection device at delivery standard version with insulated neutral on the unit s earth...

Page 19: ...ng handling operations use and maintenance For safety reasons all operations must be carried out by staff with the necessary skills and using suitable equipment Maintenance must be carried out on a re...

Page 20: ...th the positive terminal Observe the polarity of the battery terminals when connecting it as this could cause serious damage to the electrical equipment Some units require a running in period Contact...

Page 21: ...performs 6 starting attempts If the generating set does not start after these 6 attempts see the section on Resolving minor faults The APM202 automatically performs 6 starting attempts If the generat...

Page 22: ...d regularly check the level The oil level must be between the minimum and maximum marks on the dipstick If the oil level is too low keep topping it up If the oil level is too high drain some off 4 Ref...

Page 23: ...nd sudden movements should be avoided Ensure that the place where it is to be stored or used is carefully prepared beforehand Before any fixed installation on a trailer or inside a vehicle consult one...

Page 24: ...ition and correctly connected NO Check the spark plug s YES The devices to be used have not been connected prior to starting NO Disconnect the devices then try to restart the generating set YES The AP...

Page 25: ...Acoustic pressure at 1 m 83 dB A Measurement uncertainty 0 4 dB A Engine type CH440E_C5 Maintenance kit RKS2 Recommended fuel Unleaded petrol Fuel tank capacity 18 L Recommended oil 10W30 Oil sump cap...

Page 26: ...14 in application of the harmonized standards EN 60034 1 2010 COR 2010 EN 61000 6 1 2007 EN 61000 6 2 2005 COR 2005 EN 61000 6 3 2007 AMD1 2011 AMD1 COR 12 EN 55011 2009 AMD 1 2010 Relating to the res...

Page 27: ...arising out of material damage which includes but is not limited to the following Any operating losses costs or expenses resulting from unavailability of the unit etc The warranty is limited to the c...

Page 28: ...f the latter under the terms of the contract or when carried out under its responsibility Article L211 5 To comply with the contract the goods must 1 Be suitable for the use customarily expected of si...

Reviews: