32
TS_616_08 PW8000DPA ST (S2) User Manual 21/4/22
3
Installation Planning
3.1
Introduction
A certain amount of pre-planning will help ensure a smooth and trouble-free UPS installation process.This chapter
contains essential information concerning the environmental, mechanical and electrical requirements that should be
considered when planning the installation of the PowerWAVE 8000DPA ST (S2) UPS system.
3.2
Environmental and mechanical planning
3.2.1 Environmental considerations
It is essential that the following environmental guidelines are observed when planning a suitable UPS location and
operating environment.
1. The route between the equipment off-loading point and the installation location must allow the equipment to be
transported in an upright position.
2. The floor at the proposed installation site and en-route from the off-loading point must be able to safely take the weight
of the UPS and battery equipment plus any transport aids used during transit.
3. Locations with high ambient temperature, moisture or humidity must be avoided.
a) The installation site humidity should be <95% non-condensing.
b) The specified equipment ambient temperature is 0°C to +40°C but ideally this should be around 20°C to 25°C.
c) A battery temperature of 20°C to 25°C is recommended to achieve a long battery life.
d) The air conditioning system must be able to provide a sufficient amount of cooling air to keep the room within the
prescribed temperature range.
e) The air entering the UPS must not 40°C.
4. To obtain the best system performance the following environmental conditions should also be considered:
a) Fire protection standards must be respected.
b) The location must be free of dust and corrosive, or explosive, gases.
c) The location must be vibration free.
d) If the UPS is located in bayed enclosures, partition walls must be installed.
e) The minimum cabinet clearances described below must be provided.
3.2.2 Installation
The PowerWAVE 8000DPA ST (S2) is designed as a modular system contained in a range of UPS cabinets as illustrated
in the table below.
Key Point:
If you are installing an external battery cabinet supplied by Kohler Uninterruptible Power Ltd you
should refer to the manual that is provided with the cabinet for installation requirements.
ST-40
ST-60
ST-80
ST-120
ST-200
Dimensions (WxHxD) mm
550 x 1135 x 775
550 x 1975 x 775
550 x 1135 x 775
550 x 1975 x 775
550 x 1975 x 775
Maintenance Accessibility
*Totally front accessibility for service and maintenance
Input/Output Power Cabling
From the bottom front
*Note:
The battery fuses are located on the back of the ST-200 cabinet and rear access is required to operate the equipment. See
Figure 3.2 for optional installation positioning of the ST200 cabinet.