2: General Description
Module / System operational status mimic
When a UPS ‘module level’ screen is accessed it’s display is similar to the default ‘system-level’ screen, except that the
mimic display and metering refers specifically to the selected UPS module.
Figure 2.24 Operational status mimic display
Module / System ON-LINE
This is the normal mimic indications for a
(standard)
ON-LINE
UPS.
1. The rectifier and inverter are working
normally.
2. The battery is charging.
3. The bypass line is live and available.
Module / System ON-BYPASS
This is the normal mimic indications if the
UPS is operating in ECO mode. In the case
of a standard ON-LINE UPS it indicates that
either the UPS has a fault/overload which
has transferred its output to the bypass, or
the number of off-line modules has
exceeded the system redundancy.
1. The rectifier is working normally.
2. The battery is charging.
3. The inverter is turned OFF.
Module / System
ON MAINTENANCE BYPASS
This mimic indicates that the maintenance
bypass isolator is closed and the UPS output
is connected to the bypass supply through
both the ‘maintenance’ and ‘static’ bypass
lines in parallel.
1. The rectifier is working normally.
2. The battery is charging.
3. The Inverter is turned OFF.