Electrical Setting Page 1
➢
Output Voltage: Select the output rated voltage.
◼
There are four options, 208V, 220V ,230V and 240V.
➢
Output Frequency: Select output rated frequency.
◼
50Hz:
The output frequency is setting for 50Hz.
◼
60Hz:
The output frequency is setting for 60Hz.
➢
CVCF Mode (constant voltage and constant frequency function)
◼
Enable:
CVCF function is enabled. The output frequency will be fixed at 50Hz or 60Hz according to
setting of “OP Freq.”. The input frequency could be from 4
6Hz to 64Hz.
◼
Disable:
CVCF function is disabled. The output frequency will synchronize with the bypass
frequency within 46~54 Hz for 50Hz system or within 56~64 Hz for 60Hz system. Disable is the
default setting.
➢
Bypass Forbid:
◼
Enable
: Bypass forbid is enabled. When selected, running in Bypass mode under any situations is
disabled.
◼
Disable:
Bypass forbid is disabled. When selected, UPS will run in Bypass mode depending on
“Bypass at UPS off” setting. It is the default setting.
➢
NeutralLineCheck: Indicates neutral loss detection function
◼
Disable: Disable the neutral loss detection function. The UPS will not detect the neutral loss or not.
◼
Auto: The UPS will automatically detect the neutral is lost or not. If neutral loss is detected, an
alarm will be generated. If the UPS is turned on, it will transfer to battery mode. When neutral is
restored and detected, the alarm will be muted automatically, and the UPS will go back to normal
mode automatically
◼
Check: The UPS will automatically detect the neutral loss. If neutral loss is detected, an alarm will
be generated. If the UPS is turned on, it will transfer to battery mode. When neutral is restored,
the alarm will NOT be muted automatically, and the UPS will NOT go back to normal mode
automatically.
➢
ISO Compensation:
When the UPS output is connected to a transformer, the attenuation voltage of the
voltage regulator is compensated