background image

2

TT-585 3/95

6. Secure strip heater assemblies to stator with lock

nuts (X-101-8). Position strip heaters with the AC
terminals closest to the end bracket of the
generator set. See Figure 1.

7. Open circuit breaker to AC power source. With

customer-supplied leads and terminals, connect
strip

heaters

to

AC

voltage

source

using

appropriate wiring diagram in Figure 2.

8. Replace junction box side panels.

9. Close circuit breaker to AC power source.

10. Reconnect generator set to load by closing line

circuit breaker or reconnecting output leads to
transfer switch. Reconnect engine starting battery,
negative (--) lead last.

3 in.

(76 mm)

+/- 0.25

6 in.

(152 mm) +/- 0.25

Screw *

(X-465-8)

Washer

(X-25-40)

Strip

Heater

(291269)

Nut, Hex *

(X-81-1)

Nut, Lock

(X-101-8)

Bottom of Stator

Assembly

See Side & Top Views

Below

End View

* Hand-tighten only

End Bracket

End

1 in.

(25.4

mm)

5-1/4 in.

(133.35

mm)

Drill Four 9/32 in. (7.14 mm) Holes in Stator Shell

Strip

Heater

(291269)

Side View

Top View

Install AC Lead

Terminals Perpendicular to Strip Heater

Y-253000-D

Figure 1.

Generator Heater Installation

CB-272000

120 Volt Connection Diagram

240 Volt Connection Diagram

120 Volt

Strip Heater

(291269)

120 Volts AC

240 Volts AC

120 Volt

Strip Heater

(291269)

120 Volt

Strip Heater

(291269)

120 Volt

Strip Heater

(291269)

Figure 2.

Heater Kit Wiring Diagrams

Parts List

KITS: PA-253213/PA-253213-SD

Qty.

Description

Part Number

8

Washer, plain

X-25-40

4

Nut, elastic stop

X-101-8

4

Screw, 1/4-20 x 1 1/4

X-465-8

4

Nut, spiral lock

X-6210-2

2

Heater, strip

291269

Reviews: