9
1393517-W2-D
10.
Position the shower unit where the controls are at a convenient height for the
user. Position the showerhead so that the water sprays in line with the bath or
across the opening of a shower cubicle. The installation must not cause the
shower hose to be kinked during normal use.
11.
The water supplies to this product should be isolated if the product is not to be
used for a long period of time. If the product or pipework is at risk of freezing
during this period they should also be drained of water.
12.
The position of the shower and shower fittings must provide a minimum air
gap of 25 mm between the showerhead and the spill over level of any bath,
shower tray or basin. There must be a minimum distance of 30 mm between
the showerhead and the spill over lever of any toilet, bidet or other appliance
with a Fluid Category 5 backflow risk.
Zone of
Backflow
Risk
30 mm
Minimum
Toilet or Bidet
FC5
Hand Basin
FC3
Bath or Shower
Tray FC3
Shower
Unit
25 mm
Minimum
25 mm Minimum
Note : There will be occasions when the hose retaining ring will not provide a suitable
solution for Fluid Category 3 installations. In these instances an outlet double
checkvalve must be fitted, this will increase the required supply pressure typically
by 10 kPa (0.1 bar). Double checkvalves fitted in the inlet supply to the appliance
cause a pressure build up, which affects the maximum static inlet pressure for the
appliance and must not be fitted. For Fluid Category 5, double checkvalves are
not suitable.