TP-6833 2/16
14 Section 2 Installation
2.5 Manual Operation, Model KCS
Standard- Transition Switches
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
DANGER
Servicing the transfer switch. Hazardous voltage can
cause severe injury or death.
Deenergize all power sources
before servicing. Turn off the main circuit breakers of all
transfer switch power sources and disable all generator sets
as follows: (1) Press the generator set off/reset button to shut
down the generator set. (2) Disconnect power to all battery
chargers. (3) Disconnect all battery cables, negative (--) leads
first. Reconnect negative (--) leads last when reconnecting the
battery cables after servicing. Follow these precautions to
prevent the starting of generator sets by an automatic transfer
switch, remote start/stop switch, or engine start command
from a remote computer. Before servicing any components
inside the enclosure: (1) Remove all jewelry. (2) Stand on a
dry, approved electrically insulated mat. (3) Test circuits with a
voltmeter to verify that they are deenergized.
Note:
A manual operation handle is provided on the
transfer switch
for maintenance purposes only
. Do
not use the manual operation handle to transfer
the load with the power connected.
Use the manual operation handle to check the manual
operation before energizing the transfer switch. Use the
following manual operation procedures to verify that the
contactor operates smoothly without binding.
Note:
A contactor in normal and serviceable condition
operates smoothly without binding. Do not place
the transfer switch into service if the contactor
does not operate smoothly; contact an
authorized distributor/dealer to service the
contactor.
2.5.1
Manual Operation, 30--200 Amp
Standard-Transition Switches
The 30--200 amp standard-transition models have an
attached manual operating handle. See Figure 2-3.
Manual Operation Test Procedure, 30--200 Amp
Transfer Switches
1. Disable the generator set to prevent starting and
disconnect all power sources before manually
operating the transfer switch.
2. Turn the attached handle to manually operate the
transfer switch. See Figure 2-3. It should operate
smoothly without any binding. If it does not, check
for shipping damage or construction debris.
3. Return the transfer switch to the Normal position.
1
127a
1. Handle
Figure 2-3
Manual Operation Handle, 30--200 Amp
Model KCS
2.5.2
Manual Operation, 225--4000 Amp
Standard-Transition Switches
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
DANGER
NOTICE
Improper operator handle usage.
Use the manual operator
handle on the transfer switch for maintenance purposes only.
Return the transfer switch to the normal position. Remove the
manual operator handle, if used, and store it in the place
provided on the transfer switch when service is completed.
The 225--4000 amp standard-transition models use a
detachable manual operating handle.
Manual Operation Test Procedure, 225--1200 Amp
Standard-Transition Transfer Switches
1. Disable the generator set to prevent starting and
disconnect all power sources before manually
operating the transfer switch.
2. Remove the maintenance handle from the clip(s)
on the left side of the transfer switch frame. See
Figure 2-4.