TP-6835 9/17
67
Section 7 Bypass, Isolation, and Manual Transfer
Position
window:
CONN
Clockwise – draws in
the transfer switch
Figure 7-47
Isolation Handle Turned to CONN
E
L
N
Automatic Transfer Switch
Bypass Switch
Turn crank
clockwise
until window
shows
CONN.
TS CONNECTED
Upper amber light
should be on.
TS TEST
TS ISOLATED
Figure 7-48
TEST to CONN (Connected) Position
7.3.4
Return Bypass Switch to OPEN,
800--1200 Amp Models
This procedure explains how to return the bypass switch
handle to the OPEN position. The bypass handle must
be in the CLOSED position (yellow indicator on
NORMAL or EMERGENCY) and the isolation handle
must be in the CONN position (window). See
Figure 7-49, Figure 7-50, and Figure 7-51.
Note:
You can only bypass to the same source that is
connected to the ATS. A solenoid interlock
prevents incorrect operation.
Indicator shows green
when the ATS is not
bypassed.
Indicator shows
yellow when ATS is
bypassed to
Emergency.
Indicator shows
yellow when ATS is
bypassed to
Normal.
Figure 7-49
Bypass Handle and Position Indicators
E
L
N
Turn
Bypass
Handle
clockwise.
ATS
Bypass Switch
Figure 7-50
Opening Bypass to Normal
Summary of Contents for KBC
Page 26: ...TP 6835 9 17 26 Section 2 Installation Notes...
Page 44: ...TP 6835 9 17 44 Section 4 Communication and Accessory Connections Notes...
Page 48: ...TP 6835 9 17 48 Section 5 Functional Tests and Setup Notes...
Page 50: ...TP 6835 9 17 50 Section 6 Scheduled Maintenance Notes...
Page 76: ...TP 6835 9 17 76 Section 7 Bypass Isolation and Manual Transfer Notes...
Page 79: ......