Section 7 Bypass, Isolation, and Manual Transfer
Position
window: TEST
Clockwise draws in
the transfer switch
Figure 7-22
Isolation Handle Turned to TEST
WARNING
Hazardous voltage.
Can cause severe injury or death.
Close and secure the enclosure door
before energizing the transfer switch.
2. Turn the Isolation Handle clockwise (approx.
6 turns) until the window shows TEST and TS
TEST light comes on.
See Figure 7-21 and
Figure 7-22.
Note:
The ATS can be tested now without load
interruption.
3. Observe which bypass switch position window
indicator is yellow (NORMAL or EMERGENCY) at
the bypass switch handle. This indicates the
source connected to the load.
Note:
A solenoid interlock prevents you from
closing the isolation contacts until the ATS is
in the
same
position as the bypass switch.
4. Observe which Transfer Switch Connected To light
is on (Normal or Emergency) on the door. This is
the position of the transfer switch. If it is
not
in the
same position as the bypass handle, change the
position of the transfer switch as shown in
Figure 7-23.
Operate to NORMAL
Operate to
EMERGENCY *
Turn
Transfer Control
switch to Retransfer Delay
Bypass
.
Turn
Transfer Control
switch to Transfer Test (hold
15 seconds).
Connected To Normal
light should come on.
Connected To Emergency
light comes on.
* With Normal available, the automatic transfer switch will return
to the Normal position after the retransfer time delay.
Figure 7-23
Changing Transfer Switch Position
Note:
Do not close the isolation contacts unless
the transfer switch (ATS) and bypass switch
are in the same position!
5. When the transfer switch is in the
same
position as
the bypass switch handle, continue turning the
isolation handle clockwise (about 8 turns) until the
window shows CONN (connected).
Position
window: CONN
Clockwise draws in
the transfer switch
Figure 7-24
Isolation Handle Turned to CONN
Summary of Contents for KBC
Page 26: ...TP 6835 9 17 26 Section 2 Installation Notes...
Page 44: ...TP 6835 9 17 44 Section 4 Communication and Accessory Connections Notes...
Page 48: ...TP 6835 9 17 48 Section 5 Functional Tests and Setup Notes...
Page 50: ...TP 6835 9 17 50 Section 6 Scheduled Maintenance Notes...
Page 76: ...TP 6835 9 17 76 Section 7 Bypass Isolation and Manual Transfer Notes...
Page 79: ......