Reinstall the DC Sensor
NOTE:
The DC sensor must be installed as shown in the
illustration.
Hold the cap horizontally with the sensing holes down and align
the DC sensor with the cap.
Slide the DC sensor into the cap until the sensor eyes align with
the holes in the cap.
Using a 3/32
″
hex wrench, tighten the screw on the wedge lock
system (not shown) that holds the DC sensor in place in the cap.
Connect the DC sensor connector to the solenoid connector on the
valve. Ensure that the connector pair is fully seated.
Locate the connector assembly adjacent to the sensor body to
prevent pinching when cap is reinstalled on the valve.
Place the cap on the valve body.
Align the sensor eyes toward the user.
NOTICE:
Do not overtighten the setscrew. The plastic threads can be
easily damaged.
Secure the cap with the setscrew.
Open the control stop, reinstall the cap, then tighten firmly with a
strap wrench.
Verify the valve functions.
Cap
Setscrew
DC Sensor with Clip
DC Sensor
Connector
Kohler Co.
9
1108709-5-C