Electrical Installation
Cable Size
¨
Remember to SWITCH OFF the mains before carrying out any electrical
work. Refer to cable size table for the correct cable size.
¨
Use double insulation cable of over 2.5 mm
2
.
¨
Lead the power cable from MCB to a “ON/OFF’’ double pole linked switch
(If applicable) having a contact separation of at least 3 mm in all poles
outside the bathroom, then lead a cable to the terminal block inside the
heater unit.
¨
Cut a small groove on the rubber seal “A“ (at the back of heater base) with
a cutter for cable inserting.
Voltage
(AC)
Power
(Watt)
Current
(A)
Cable Size
(mm
2
)
On/Off
Switch (A)
Fuse/MCB
(A)
~220V
50/60 Hz
3500
15.9
2.5
32
32
4500
20.5
2.5
32
32
6000
27.3
4.0
32
32
DANGER: Risk of electrical shock.
This appliance must be earthed.
Improper grounding could cause electrical shock.
Fuse Distributor Board
Miniature Circuit Breaker (MCB)
FUSE
ON/OFF
Double PVC cable over 2.5 mm
2
ON/OFF Double Pole Switch
Cable
Note:
For the correct size of wire conductor corresponding to
different electrical loadings, refer to Cable Size table.
1237889-X2-G 12
Kohler Co.