TP-6120 5/02
19
Section 3 General Troubleshooting
Is the
controller
fault LED
lit?
Yes
Correct fault
and resume
troubleshooting.
No
Have fuel supply
installer purge
air.
Are spark plug wire
connections okay?
Reconnect and/or
tighten.
Does the battery lose
charge while the
system is running?
Check the battery charging
system.
No
Is air cleaner
plugged?
Possible generator set
overload. Does reducing
load solve problem?
(Open circuit breaker to
reduce load.)
Clean or replace air
cleaner elements.
Yes
Reduce the load to keep
it within the rated range.
Lacks Power or Runs Erratically
No
Yes
No
Are spark plugs okay?
See Section 2.6.2.
Regap or replace.
Yes
Go to
D
C
Is fuel
pressure
7-11 in. water?
Yes
Have fuel supply installer
correct fuel pressure
problem.
Ensure that the
main connector is
tightly connected.
Yes
No
No
Yes
No
No
Yes
Has air
been purged
from fuel
lines?
Summary of Contents for COM7.5
Page 1: ...Commercial Generator Sets Models COM7 5 TP 6120 5 02 Service ...
Page 14: ...TP 6120 5 02 4 Section 1 Specifications Notes ...
Page 22: ...TP 6120 5 02 12 Section 2 Scheduled Maintenance Notes ...
Page 32: ...TP 6120 5 02 22 Section 3 General Troubleshooting Notes ...
Page 52: ...TP 6120 5 02 42 Section 7 Wiring Diagrams Figure 7 1 Wiring Diagram GM20551 ...
Page 53: ...TP 6120 5 02 43 Section 7 Wiring Diagrams Figure 7 2 Schematic ADV 6654 ...
Page 54: ...TP 6120 5 02 44 Section 7 Wiring Diagrams Notes ...
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......