Section 3 General Troubleshooting
Yes
Correct the problem.
Ignition system problem. Refer
to the Engine Service Manual.
Clean/replace air
cleaner elements.
See Section 2.4.
Engine problem. See the
Engine Service Manual.
Yes
A
Is fuel supply
turned on?
Check/replenish fuel
supply.
Yes
No
Turn on fuel supply.
Is gas pressure to system
within specifications?
Have gas provider or
owner correct fuel
pressure problem.
No
Is there an audible click
indicating fuel solenoid opening
when the unit starts to crank?
Check/repair wiring.
No
Yes
Yes
No
No
Go to
B
Is fuel supply
low?
No
Yes
No
Have the fuel supply
installer purge the fuel
lines.
Has the air been purged
from the fuel lines?
No
No
Yes
Does unit start?
Yes
Is there a spark?
No
Did a fault
shutdown
occur?
Yes
Yes
Correct the fault and reset the
controller.
Is the air cleaner
dirty or plugged?
Is the fuel hose
pinched?
Summary of Contents for COM7.5
Page 1: ...Commercial Generator Sets Models COM7 5 TP 6120 5 02 Service ...
Page 14: ...TP 6120 5 02 4 Section 1 Specifications Notes ...
Page 22: ...TP 6120 5 02 12 Section 2 Scheduled Maintenance Notes ...
Page 32: ...TP 6120 5 02 22 Section 3 General Troubleshooting Notes ...
Page 52: ...TP 6120 5 02 42 Section 7 Wiring Diagrams Figure 7 1 Wiring Diagram GM20551 ...
Page 53: ...TP 6120 5 02 43 Section 7 Wiring Diagrams Figure 7 2 Schematic ADV 6654 ...
Page 54: ...TP 6120 5 02 44 Section 7 Wiring Diagrams Notes ...
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......