ADVANCED menu
Warning
Menu reserved to the machine manufacturer.
To open the advanced menu, enter the password “5 4 8” in the password input page, as follows:
•
Press the UP and DOWN buttons together and hold them pressed for about 5 seconds until the password input page is
displayed.
•
Enter the password "5 4 8" by pressing the DOWN button (ref. 9 p. 23) to select the right digit in the right position, then press
the UP button (ref. 8 p. 23) to validate the digit.
To open the advanced menu, input the password “5 4 8” in the password input page.
From this menu it is possible to modify the parameters for the management and control of ATS45.
Unlike the basic menu, the advanced menu has also two submenus.
Engine menu
Page
Description
CRANKING
THRESHOLDS
Electric motor start thresholds are set by the ECU. The parameters refer to engines only.
- 1-D+ THRESHOLD: Voltage value below which the battery is not charging
- 2-RPM THRESHOLD: Speed value above which the engine is on
- 3-START: engine starting mode (automatic/manual)
- 4-NO. OF CRANKING: max number of cranking attempts before the misfire alarm is triggered
- 5-CRANKING TIME: maximum engine cranking time
- 6-PAUSE TIME: time in seconds between two cranking attempts
- 7-ENGINE DETECTION DELAY: Engine on detection delay.
BATTERY ALARM
When you open this menu, a list of battery parameters is displayed:
- 1-L-Vdc-BAT: Voltage value in Volt under which an alarm is triggered
- 2-H-Vdc-BAT: Voltage value in Volt above which an alarm is triggered.
SERVICE
From this menu you can set a countdown hour meter indicating the hours to next service.
For the Service Due alarm to be triggered you have to activate it.