TP-6329 8/07
40
Section 5 Controller
TP6196
Move the generator set master switch to the RUN position. The generator set
engine starts and the controller display shows the engine runtime hours.
Display :*
or
To raise or lower the voltage in large increments
(approximately 5--7 volts per step).
To enter fine voltage adjustment mode.
To raise or lower the voltage in smaller increments
(approximately 0.5--0.7 volts per step).
or
Hold:
Wait about 5 seconds until the display changes from runtime hours
to the program version number.
Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller “password.”)
x x
x x x x
1 P
1 P
* Shaded boxes show which character in the controller display changes for each adjustment.
X
in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.
x.
The controller is now in the voltage coarse adjustment mode.
Press:
1 P
Continued on Figure 5-7.
x x
x x
x
x
Output Voltage Adjustment Mode:
Figure 5-6
Output Voltage Adjustments
Summary of Contents for 15RYG
Page 1: ...Commercial Generator Sets Models 15 30RYG TP 6329 8 07c Installation...
Page 32: ...TP 6329 8 07 32 Section 3 Installation Instructions Notes...
Page 42: ...TP 6329 8 07 42 Section 5 Controller Notes...
Page 46: ...TP 6329 8 07 46 Section 6 Generator Reconnection Notes...
Page 60: ...TPMPFP 6329 8 07 60 Notes...
Page 61: ...TPMPFP 6329 8 07 61 Notes...
Page 62: ...TPMPFP 6329 8 07 62 Notes...
Page 63: ......