TP-6329 8/07
36
Section 5 Controller
Battery voltage (Bt).
This setting toggles between 12
and 24 VDC for the engine starting battery voltage. The
15/30RYG uses a 12-volt battery, Bt12.
Communications setting (Cn).
This setting allows the
user to set the controller for communication with
optional meters. The 15/30RYG is factory-set for no
CAN communications, Cn00. Change this setting if the
optional Remote Digital Gauge is used.
Parameter
Setting
Description
Voltage, VAC
Frequency, Hz
Phases, Wires
Connection
Unit’s system voltage and
frequency, 15RYG
Uu01
120/240
60
Single phase, 3 Wire
1 PH
Uu04
277/480
60
Three phase, 4 Wire
Wye
Uu10 *
120/240
60
Three phase, 4 Wire
Delta
Uu10 *
139/240
60
Three phase, 4 Wire
Wye
Uu11 *
120/208
60
Three phase, 4 Wire
Wye
Uu16 *
127/220
60
Three phase, 4 Wire
Wye
Unit’s system voltage and
frequency, 30RYG
Uu01
120/240
60
Single phase, 3 Wire,
1 PH
Uu03
230/400
50
Three phase, 4 Wire
Wye
Uu04
277/480
60
Three phase, 4 Wire
Wye
Uu07 *
110/220
50
Single phase, 3 Wire
1 PH
Uu10 *
120/240
60
Three phase, 4 Wire
Delta
Uu10 *
139/240
60
Three phase, 4 Wire
Wye
Uu11 *
120/208
60
Three phase, 4 Wire
Wye
Uu16 *
127/220
60
Three phase, 4 Wire
Wye
Uu17 *
110/190
50
Three phase, 4 Wire
Wye
Uu17 *
110/220
50
Three phase, 4 Wire
Delta
Uu18 *
120/208
50
Three phase, 4 Wire
Wye
Uu21 *
220/380
50
Three phase, 4 Wire
Wye
Uu22 *
240/416
50
Three phase, 4 Wire
Wye
Uu23 *
115/200
50
Three phase, 4 Wire
Wye
Unit configuration
Uc01
Standby
Engine type
Ec03
15RYG
Ec06
30RYG
Engine data input types
Ed01
15/30RYG factory setup
Battery voltage
Bt12
12 VDC
Communications
Cn00
No CAN communications
Cn01
J1939 (use for Remote Digital Gauge)
Cn06
[
Enables J1939 communications and 1-hour ADC power down after engine stop
for either:
a. Remote start/stop switch
b. Automatic transfer switch
c. Remote Digital Gauge with remote start/stop switch and replacement harness
* ADC application program version 1.20 or higher
[
ADC application program version 1.21 or higher
Figure 5-1
Configuration Parameters
Summary of Contents for 15RYG
Page 1: ...Commercial Generator Sets Models 15 30RYG TP 6329 8 07c Installation...
Page 32: ...TP 6329 8 07 32 Section 3 Installation Instructions Notes...
Page 42: ...TP 6329 8 07 42 Section 5 Controller Notes...
Page 46: ...TP 6329 8 07 46 Section 6 Generator Reconnection Notes...
Page 60: ...TPMPFP 6329 8 07 60 Notes...
Page 61: ...TPMPFP 6329 8 07 61 Notes...
Page 62: ...TPMPFP 6329 8 07 62 Notes...
Page 63: ......