TP-6196 5/04
18
Section 3 Troubleshooting
Troubleshooting Chart, continued
Problem
Reference
Corrective Action
Possible Cause
Stops
suddenly
Fault shutdown
Check for a fault shutdown code on the controller’s LED
display. Correct the fault and then move the generator
set master switch to OFF/RESET to reset the controller.
Section 4.4
Section 5.9
No fuel
Turn on fuel supply.
—
Fuel line restriction
Inspect fuel lines.
—
Fuel lines too long
Check fuel line length.
Section 5.10.1
Air cleaner clogged
Replace element.
Section 2.4
Blown controller fuse (F3)
Replace fuse.
Section 5.11
Blown auxiliary winding fuse (F1)
Replace fuse. If fuse blows again, test generator
components.
Section 5.11
Blown relay interface board (RIB)
fuse (F2)
Replace fuse.
Section 5.11
Spark plug(s)
Replace and regap plug(s).
Engine S/M
Engine overheated (hot engine
only)
Check air intake, fuel adjustment, oil level, air
inlet/outlet.
Section 2.5
Section 2.2
Section 5.10
Low oil pressure (LOP) switch
Attempt startup. If unit shuts down, remove lead from
LOP switch and reset controller. A successful restart
attempt indicates a faulty LOP shutdown switch.
Note:
Check engine oil pressure before performing test
and/or replacing LOP shutdown switch.
Section 2.2.1
Section 5.9.2
Fuel valve/fuel regulator
Check regulator/valve operation.
Section 2
Section 6
Engine overloaded
Reduce electrical load.
Section 1.2
Loss of generator output voltage
to controller
Check connections at P15 plug.
Check continuity of AC sensing leads 11 and 44.
Section 7
Magnetic pickup connections
Check for loose connections to the mag pickup.
Section 5.8
Ignition module
Test and/or replace.
Engine S/M
K3 (flash) relay
Check for Flash LED illumination. Check RIB fuse.
Replace relay board.
Section 4.8
Operates
i
ll
Air cleaner clogged
Replace element.
Section 2.4
p
erratically
Spark plug(s)
Replace and regap plugs.
Section 2.3
Spark plug wire(s)
Replace spark plug wires.
Engine S/M
DSAM leads incorrectly
connected or disconnected
(12RES only)
Connect for natural gas. Disconnect for LP.
Section 5.10.5
Fuel line restriction
Check fuel lines.
Section 5.10.1
Fuel mixture adjustment incorrect Check and/or adjust.
Section 5.10
Magnetic pickup connections
Check for loose connections to the mag pickup.
Section 5.8
Governor adjustment incorrect
Adjust governor stability.
Section 5.8
Section 4.5
Ignition system
Test and/or replace components.
Engine S/M
Inadequate cooling (hot engine
only)
Inspect air inlet and outlet.
Section 2.5
Carbon buildup in engine
Clean cylinder head.
Engine S/M
Engine valves not seating
correctly
Check cylinder pressures with leakdown test. Inspect
valves and valve seats.
Engine S/M