TP-7045 3/18c
65
Section 9 Paralleling Generator Sets
Step Potential Cause
Explanation
Troubleshooting
Fault: Close Attempt
Fault: Fail to Close
(Continued)
7
Breaker is not powered
The 24V electronics on the circuit breaker
require an external 24V source on a 12V
generator.
Verify the 24V input which exists on
paralleling generators is receiving 24VDC
in the correct polarity.
8
Wiring to power is not
complete
There is no voltage to the CB close relay
on this circuit breaker.
Connect the supply to the CB close relay to
either 24V from wire #70 or an external
24VDC supply (with battery storage).
9
Breaker status feedback
is not valid, no bus
sensing
The breaker closes but the controller does
not see a change in status. The controller
cannot see the bus is energized as the bus
sensing is not connected correctly on any
generators on the network.
Verify the wiring on the circuit breaker to
ensure that it is connected correctly. Verify
bus wiring for all nodes. Verify the
generator output is connected to the line
side of the generator breaker.
Fault: CB Status
Warning: Bus Sensing Not Connected
1
Breaker status feedback
is not valid, no bus
sensing
The breaker closes but the controller does
not see a change in status. The controller
cannot see the bus is energized as the bus
sensing is not connected correctly on this
generator, but another generator is
connected.
Verify the wiring on the circuit breaker to
ensure that it is connected correctly. Verify
bus wiring for this generator.
Fault: CB Status or Continuous Breaker Cycling
1
Breaker status feedback
is not valid
The breaker closes but the controller does
not see a change in status. The controller
sees the bus is now live.
Verify the wiring on the circuit breaker to
ensure that it is connected correctly.
Summary of Contents for 12EFKOZD
Page 2: ...TP 7045 3 18c 2...
Page 8: ...TP 7045 3 18c 8 Safety Precautions and Instructions Notes...
Page 12: ...TP 7045 3 18c 12 Section 2 Location Lifting and Mounting Notes...
Page 24: ...TP 7045 3 18c 24 Section 4 Exhaust System Notes...
Page 28: ...TP 7045 3 18c 28 Section 5 Fuel System Notes...
Page 34: ...TP 7045 3 18c 34 Section 6 Electrical System Notes...
Page 50: ...TP 7045 3 18c 50 Section 7 Installation Drawings Notes...
Page 54: ...TP 7045 3 18c 54 Section 8 Reconnection Figure 8 3 Generator Reconnection ADV 5875F U...
Page 81: ...TP 7045 3 18c 81...
Page 82: ...TP 7045 3 18c 82...
Page 83: ...TP 7045 3 18c 83...