Section 7 Component Testing and Adjustment
Preliminary Adjustment Procedure
1. Place the generator set master switch in the OFF
position. Do not run the generator set.
2. Set the control unit “I” adjustment one division from
zero, the “D” adjustment four divisions from zero,
and the gain adjustment at the third division from
zero.
3. For
isochronous
operation,
turn
the
droop
adjustment
potentiometer
counterclockwise
(CCW) to the minimum position.
For droop
operation, turn the droop potentiometer to the
desired droop.
Droop adjustment may be
necessary with parallel generator operation.
Note:
If the governor uses the full stroke of the
actuator shaft and the linkage adjustment
uses only the active fuel range, the
maximum
obtainable
droop
would
be
approximately 12% at full load.
4. Position the actuator lever to hold the fuel pump
lever in the STOP position when the power is off.
Adjust the actuator linkage for smooth, non-binding
operation.
Final Adjustment Procedure
1. Place the generator set master switch in the RUN
or TEST position to start the generator set.
2. Adjust the control unit speed potentiometer until
the engine operates at the desired rpm (50 or
60 Hz on the frequency meter).
3. If governing is unstable, turn the “I” and gain
potentiometers slightly CCW.
Note:
Except for the speed potentiometer, control
unit potentiometers have internal stops at 0
and 100%.
4. With the engine running at no load, finalize the “I”,
“D”, and gain adjustments.
5. Slowly turn the gain adjustment potentiometer
clockwise (CW) until the output shaft and linkage
oscillates.
Slowly turn the gain adjustment
potentiometer CCW until the actuator lever
stabilizes.
6. Jog the actuator lever by hand. If the actuator lever
oscillates three to five times and then stabilizes, the
gain setting is correct.
7. Turn the gain potentiometer one division CCW.
8. Turn the “D” adjustment fully CW while observing
the actuator shaft. If the lever does not become
unstable, jog it by hand. When the lever oscillates,
turn the “D” adjustment CCW slowly until the
actuator shaft stabilizes. Jog the lever again, it
should oscillate 3--5 times and then become stable.
If the system response to load changes is
satisfactory at this point, omit step 9 and proceed to
step 10.
9. Turn the “I” potentiometer fully CW and watch the
actuator shaft.
If the actuator lever does not
become unstable, jog it by hand.
When the
actuator lever slowly oscillates, slowly turn the “I”
potentiometer CCW until the lever stabilizes.
10. Jog the actuator lever by hand. It should oscillate
3--5 times before stabilizing. The governor is now
calibrated.
11. Stop the generator set.
Summary of Contents for 125EOZ/100EFOZ
Page 6: ......
Page 12: ...TP 5737 5 01 VI Safety Precautions and Instructions Notes...
Page 14: ...TP 5737 5 01 ii Service Assistance Notes...
Page 58: ...TP 5737 5 01 44 Section 5 Decision Makert 3 Troubleshooting Notes...
Page 70: ...TP 5737 5 01 56 Section 6 Decision Makert 1 Controller Troubleshooting Notes...
Page 108: ...TP 5737 5 01 94 Section 8 Disassembly Reassembly Notes...
Page 110: ...TP 5737 5 01 96 Section 9 Wiring Diagrams Notes...
Page 128: ...TP 5737 5 01 Section 9 Wiring Diagrams 114 Notes...
Page 136: ...TP 5737 5 01 122 Section 9 Wiring Diagrams Notes...
Page 145: ......
Page 146: ......
Page 147: ......