TP-5737 5/01
34
Section 5 Decision-Maker
t
3+ Troubleshooting
5.3.2
Fuses
The following chart lists the possible causes of blown
controller fuses F1, F2, and F3. If a fuse blows, replace it
and resume operation. If the fuse blows again, use
Figure 5-17 to identify the faulty component(s).
Inoperative audio/visual alarm
Blown F1 fuse (remote annunciator: 3 amp)
Blown F2 fuse (controller: 3 amp)
Battery connections reversed
Shorted DC supply to indicator panel
Shorted controller circuit board
Blown F3 fuse (engine and accessories: 15 amp)
Inoperative engine electrical components
Inoperative overvoltage board
Inoperative panel lamps, engine gauges
Inoperative dry contact kit
Remaining accessories connected to TB1-42A
Figure 5-17
Checking F1, F2, and F3 Fuses