No.

Name

Description

q

LED display (red)

Displays the detected flow rate value, setting
contents, and error content

w

Switch output indicator (red)

Lights up when switch output is ON

e

Autoscan indicator (green)

The channel whose current flow rate is displayed on
the LED lights up

r

UP key (

)

Used when adjusting set value upward

t

DOWN key (

)

Used when adjusting set value downward

y

Mode key (

)

Used for all types of settings

802

Setting procedure

Caution

Major parts and functions

1.

Since miswiring in the sensor head, or in the power supply, switch, and communication cable, can
damage both the controller and sensor head, always check the wiring before switching on the power.

2.

The setting conditions are written to EEPROM and saved. Be aware that EEPROM has a finite lifetime,
with guaranteed number of times up to 100,000 times.

3.

When using window comparator mode 2 in operations that involve repeated reference flow rate
capture, the EEPROM guaranteed number of times may be exceeded in a short period of time. In such
cases, use window comparator mode 3.

4.

In this catalog, window comparator mode 1 is called by code: CO1, window comparator mode 2 by
code: CO2, window comparator mode 3 by code: CO3, and window comparator mode 4 by code: CO4.

Setting preparation

• Connect the connectors to the sensor heads.

(See p.801 for the connection procedure for the sensor head connectors.)

• Connect the sensor heads (one to four pcs.) and the power supply, switch, and communication cable to

the controller. (See p.801 for attaching and removing of the sensor head and the power supply, switch,
and communication cable.)

Setting procedure

Window comparator mode 1 (CO1)
Window comparator mode 4 (CO4)

A. S. OUT

SW.OUT

ch

1

2

3

4

FSU

Figure 1

e

t

y

w

q

r

Output mode setting

Set each channel
to CO1, CO2,
CO3, or CO4.

Hysteresis setting

Perform the
hysteresis settings
for each channel.

Sensor head selection

Set the sensor
heads to be used
in each channel.

L1, L2 settings

Perform the L1 and L2
settings for each channel.

Various function settings

Perform function
settings for each
channel. (See
Functions List.)

Detection

Completes the
settings, and
commences
detection.

Window comparator mode 2 (CO2)
Window comparator mode 3 (CO3)

L, L2 settings

Perform the 

Δ

L and L2

settings for each channel.

Reference flow rate capture

Performs reference flow rate
capture for each channel. L1 is 
automatically created inside
the controller.
L1=Reference flow rate —

Δ

L

Settings at time of shipment (1ch to 4ch)

Sensor head type: 

±

3

R

/min 

[

±

0.11 ft.

3

/min.]

type

Output mode: Window comparator mode 1
Hysteresis: 0.02

R

/min 

[0.007 ft.

3

/min.]

L1 level: 2.00

R

/min 

[0.0706 ft.

3

/min.]

L2 level: 1.00

R

/min 

[0.0353 ft.

3

/min.] 

MULTI-CHANNEL FLOW RATE SENSOR CONTROLLERS

Summary of Contents for Flow FSU

Page 1: ...um valve ON Workpiece lifted by vacuum Vacuum break L R min L2 L1 ΔL Reference flow rate capture ON t Switch output Hysteresis Discharge to atmospheric pressure Vacuum valve ON Workpiece lifted by vacuum Vacuum break L R min L1 L2 ON t Switch output Hysteresis Hysteresis Discharge to atmospheric pressure Vacuum valve ON Workpiece lifted by vacuum Vacuum break Window comparator mode 2 When L1 has b...

Page 2: ... and controller Attempting to connect the sensor head with the power on could cause erratic operation in the controller due to surge voltage etc DANGER While the product is in operation do not attempt to adjust the attached mechanisms connecting and disconnecting the wiring connector or attach or position the sensor head etc Abnormal operations could result in injury General precautions 1 If power...

Page 3: ... be careful to avoid applying excessive force on the lead wires 4 3 2 1 1ch PSUW FS 2ch 3ch 4ch The connector for 4 sensor head Connector for power supply switch and communication cable Power supply switch and communication cable Sensor head Lock lever Lock lever Cover Sensor head side connector Attaching and removing of the sensor head and the power supply switch and communication cable Attaching...

Page 4: ...g preparation Connect the connectors to the sensor heads See p 801 for the connection procedure for the sensor head connectors Connect the sensor heads one to four pcs and the power supply switch and communication cable to the controller See p 801 for attaching and removing of the sensor head and the power supply switch and communication cable Setting procedure Window comparator mode 1 CO1 Window ...

Page 5: ...m hold Flow rate display deleted Output mode check Sensor head type check ON ΔL OFF point check Reference flow rate ΔL OFF point check Switch output condition display Version display Reference flow rate capture method using general purpose I O input 24V SW PIN 1 0 5V or less 10 ms or longer Captured at startup 1 2 3 4 PIN SW PIN 1 1 2 3 4 PIN 1 c h 4 c h Flow rate sensor head Multi channel flow ra...

Page 6: ...rocedure to switch off the flow rate display Flow rate display switch off Procedure 1 2 3 4 5 Device operation 7 seg display Remark 7 seg LED off 7 seg LED re lighted Use the following procedure to switch the flow rate display to autoscan mode Since autoscan mode is combined with the key lock function no key operation other than cancellation of autoscan can be performed Note Autoscan mode is cance...

Page 7: ...and bottom hold cannot be implemented at the same time Peak hold and bottom hold Procedure 1 2 3 4 5 6 7 Peak hold 7 seg display Remark Hold start Hold cancel Bottom hold 7 seg display Error Display Error display n is the targeted channel n is the targeted channel Error cancel In the case of a wire break shut off the power and replace the sensor head Correct the error and then press the mode key f...

Page 8: ...eresis width setting for Channel 4 HYS1 1 1 1CH 2 2CH 3 3CH 4 4CH Always input 1 Signal name DC24V 0V OUT1 OUT2 OUT3 OUT4 0V RXD TXD RTS CTS Controller side Personal computer side D sub 25 pin configuration Pin No 1 2 3 4 5 6 7 8 9 10 11 Signal name D G TXD RXD RTS CTS DSR DCD DTR Pin No 7 2 3 4 5 6 8 20 Serial communication cable Power and switch output cable D sub 9 pin configuration Signal name...

Page 9: ... Enabled for window comparator mode 4 only Function Sets switch output reversed not reversed Send example INV1 0c rl f Response example OK c rl f Response example NG c rl f 21 illegal type I N V 1 0 1 1CH 2 2CH 3 3CH 4 4CH 0 Not reversed 1 Reversed P1 1 1CH 2 2CH 3 3CH 4 4CH C Function Displays the L1 ΔL and L2 points for each channel Send example C1 c rl f Response example 1 00 c rl f L1 ΔL 0 50 ...

Page 10: ...LED Send example DIS 1 c rl f Response example OK c rl f Response example NG c rl f 21 illegal type DIS 1 1 Not lighted 0 Lighted AS Function Sets ON OFF for autoscan function Send example AS 1 c rl f Response example OK c rl f Response example NG c rl f 21 illegal type AS 1 1 ON 0 OFF PHL Function Sets ON OFF for peak hold function Send example PHL 1 c rl f Response example OK c rl f Response exa...

Page 11: ... Sensor Sensor Sensor Sensor Main circuit Main circuit Main circuit Main circuit Reference flow rate capture Reference flow rate capture Sensor head 3ch Sensor head 4ch Brown V Blue 0V Black analog voltage output Brown V Blue 0V Black analog voltage output Main circuit Multi channel flow rate sensor controller Power supply and switch output cable Brown SW4 Black 0V Yellow SW3 Green SW2 White Red V...

Page 12: ...w comparator mode 3 Window comparator mode 4 Compatible with window comparator mode 4 only Variable Can be freely set at 2 digits or more 7 segment LED 3 digit display Red LED lights up when ON Flow rate display channel green LED lights up UP DOWN MODE Conforms with RS232C 10 50 C 14 122 F storage 20 80 C 4 176 F no condensation and freezing IEC61000 4 4 Power supply line 1KV level 2 Sensor input ...

Page 13: ...o come within 1 FS of final attained voltage flow rate Within 10 sec 12 mA MAX Between all external connector terminals and body AC500V for 1 min or AC600V for 1 sec Between all external connector terminals and body 50 MΩ at DC500V megger M5 female thread brass insertion tightening torque at 2 5 N m 1 84 ft lbf or less Gas contact part PPS plastic flow path body ceramic substrate brass connections...

Page 14: ... Flow rate sensor head PM100 KB100 Mini clamp wire mount plug PSU M Power supply switch and communication cable Sensor head connecting cable Flow rate sensor head FS PSUK PSUW Communication cable Blank No communication cableNote 1 D With communication functionNote 2 Cable length 3L 3000 mm 118 in 5L 5000 mm 197 in Cable length 3L 3000 mm 118 in 5L 5000 mm 197 in Power supply switch and communicati...

Page 15: ... clamp wire mounting socket PSUK Dimensions mm in Model PSUK 3L PSUK 5L L 3000 118 5000 197 7 8 0 307 30 1 181 5 0 197 2 65 0 1043 2 M2 6 0 45 Depth 6 0 236 27 6 1 087 32 1 260 5 3 0 209 40 1 575 40 1 575 4 digit LED flow rate indicator Mode button LED red A S OUT SW OUT ch 1 2 3 4 FSU LED green DOWN button UP button 4 switch output indicators 4 autoscan channel indicators Mounting thread The conn...

Page 16: ...al communication cable Note 3 leads 7 0 276 PSUW 2 φ4 5 0 177 9 0 354 11 0 433 4 5 0 177 16 0 630 11 0 433 2 φ2 9 0 114 9 6 0 378 7 0 276 24 0 945 7 0 276 30 1 181 4 0 157 38 1 496 12 6 0 496 1 6 0 063 PSU BR Model PSUW 3L PSUW 5L L 3000 118 5000 197 Note Only PSUW D is available Hex socket head screw M2 6 0 45 length 5 0 197 2 screws provided MULTI CHANNEL FLOW RATE SENSOR CONTROLLERS Notes 1 The...

Page 17: ...for vacuum breaking flow Flow rate sensor head Vacuum Valve Unit with flow rate sensor CRCB 0064W V P R V Vacuum port R Exhaust port P Pressure port Adjusting needle for vacuum breaking flow Flow rate sensor head Micro ejector with flow rate sensor CRCB 0065W Note For detailed specification and dimension consult us ...

Reviews: