ZFC
page 36
ZFC K03/0522
PDU
ADDRESS
REGISTER
VARIABLE
RUN TIME
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 516 [h]
0x204
40517
error status (bitfield)
1
r
uint16 [d] 1: Display error
[d] 2: data-storage error
[d] 4: initialization error
[d] 8: Analog input error
[d] 16: PT100 ADC error
[d] 32: Correction calculation factor (A) error
[d] 64: Correction calculation factor (B) error
[d] 128: TPC A calculation error
[d] 256: TPC B calculation error
[d] 512: PT100 sensor1 out of range error
[d] 1024: PT100 sensor2 out of range error
Reading differential flow rate, total or accumulated total
The returned values are given including the decimals and represent the actual value.
The given value may differ from the value that is shown on the display – this is due to
the fact that the display is limited in the number of digits and may have a slower
update rate set.
For example, when two decimals are selected for total and total has a value of
123456.78 the display will show 23456.78 while communication will read a “total” of
12345678 and a “total decimals” of 2.
* Clearing total
It is possible to clear the total counter by means of writing a value of 0 to all the 3
registers of total/flow rate in a single write action. Writing any other value will result in
the reply of an error message because the registers of total/flow rate are during
operation read-only.
Setup variables
PDU
ADDRESS
REGISTER
VARIABLE
TOTAL A
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 32
[h] 0x020
40033
unit (A and B)
1
r/w
uint16 0: none
3: kg
6: usgal
1: L
4: lb
7: bbl
2: m3
5: gal
[d] 33
[h] 0x021
40034
decimals (A and B)
1 r/w
uint16
0…3
[d] 34
[h] 0x022
40035
K-factor
2 r/w
uint32
1...9999999
Representation: 0.000010…9999999 depending
on variable 54: decimals K-factor.
[d] 37
[h] 0x025
40038
decimals K-factor
1 r/w
uint16
0…6