Kobold Y-DVZ45001/PS25 Operating Instructions Manual Download Page 12

DVZ 

page 12 

 

DVZ B06/1122 

 

 
 

8.5  Main menu items 

8.5.1 

Switching point 

 

The switching point is entered in the menu item "

Spo

". A setting value between 

000 and 999 can be selected. This value can also include a decimal point. The 
decimal point can be set at two points (e.g. 10.0 or 1.00). If the measuring value 
is the set switch point, the electronic is activated and is signalised by a lightning 
LED.  
If  the  hysteresis  is  equal  to  zero  and  the  window  point  is  de-activated,  the 
electronic  switches  back  whenever  the  indicated  value  falls  below  the  switching 
point. 

 

8.5.2 

Hysteresis 

After the setting of switching point, the hysteresis can be entered as a negative 
value  in  the  "

HYS

"  menu.  The  standard  hysteresis  value  is  zero.  In  operation 

condition this can lead to ambiguous switching behaviour if the reading fluctuates 
around the switching point or window point. Aid can be given here by increasing 
the hysteresis. The hysteresis relates to the switching point and the window point 
(switching point minus hysteresis; window point plus hysteresis). 

Example:

 Switching point 20 L/min; Hysteresis: -2.5 L/min 

 

The electronic switches when 20 L/min is exceeded and switches back 
when the reading drops below 17.5 L/min. 

 

8.5.3 

Window point (duo-point) 

As well as the switching point, it is also to define a "

duo

" (duo-point), the window 

point. This must be higher than the switching point. Using the window point and 
the  switching  point  it  is  possible  to  monitor  the  measurement  value  in  a  certain 
range.  The  switching  point  limits  the  measurement  range  to  smaller  values  and 
the window point to larger values. 

Changing code

Value setting

Storing

7sec

4-20

mA

0-20

mA

Analog output

choosing

Summary of Contents for Y-DVZ45001/PS25

Page 1: ...Operating Instructions for Compact Vortex Flow Meter Model Y DVZ45001 PS25...

Page 2: ...7 Electrical Connection 8 8 Adjustments Compact Electronic 9 8 1 Button function 9 8 2 Settings 10 8 3 Value setting 10 8 4 Set up mode 11 8 5 Main menu items 12 9 Maintenance 15 10 Technical Informa...

Page 3: ...gainst an applicable postage fee The devices are only to be used maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Heal...

Page 4: ...ke fluids in pipes The device works using the vortex process making it virtually maintenance free This involves the installation of a sharp edged object the vortex generator in the flow duct A vortex...

Page 5: ...rection of arrow universal mounting Avoid pressure and radial tension Fasten the pipe at up stream and down stream at a distance of 50 mm from the connections Install the compression fitting see secti...

Page 6: ...1 rotation using an open ended spanner Making a mark will assist in correct rotation 3 3 Slightly release the nut once again to take the radial stress off the tube 3 4 Checking of fit A distinct bead...

Page 7: ...DVZ DVZ B06 1122 page 7...

Page 8: ...t the voltage values of your system correspond with the voltage values of the measuring unit Make sure that the supply wires are de energized Plug in the system according to the connecting diagrams We...

Page 9: ...onnection diagram After power on the measuring range end current will be shown for 3 seconds 8 1 Button function In the normal mode measuring mode In the set up mode Press 3 sec Setup mode Switch poin...

Page 10: ...selection SCS 0 0 mA 4 4 mA 4 mA Change Code CCo 000 999 000 Start and End value of flow relating to 0 4 20 mA If you do not remember your code number you have to send the unit back to Kobold 8 3 Valu...

Page 11: ...c Code entering Filter Windowpoint Hysteresis Switching point 3 sec Code Start current 7sec 7sec Contact function Value setting Value setting Value setting Value setting Value setting 7 levels N O N C...

Page 12: ...dition this can lead to ambiguous switching behaviour if the reading fluctuates around the switching point or window point Aid can be given here by increasing the hysteresis The hysteresis relates to...

Page 13: ...ceeded If the switching value remains between 9 L min 10 1 and 21 L min 20 1 the contact will also remain in active switching condition LED on If it exceeds 21 L min or is below 9 L min the electronic...

Page 14: ...ency 8 5 5 Current output The current output is selected in menu items S C Start current indicated value 0 4 mA E C End current indicated value 20 mA SCS Start current selection 0 20 mA or 4 20 mA The...

Page 15: ...n order to avoid problems we recommend the installation of a filter such as the magnetic filter type MFR If it is necessary to clean the sensor the sensor can be rinsed with a suitable liquid Fiber pa...

Page 16: ...rced Sensor PVDF Connections Brass Bluff body PPS fibreglass reinforced Seal NBR Response time 1 s Protection IP 65 Connection Clamp ring Serto SO 00001 15 and lock nut Serto SO 0021 15 1 2 for 15 mm...

Page 17: ...DVZ DVZ B06 1122 page 17 11 Dimensions...

Page 18: ...DVZ page 18 DVZ B06 1122...

Page 19: ...l disposal regulations and environmental regulations Batteries Batteries containing pollutants are marked with a sign consisting of a crossed out garbage can and the chemical symbol Cd Hg Li or Pb of...

Page 20: ...ogy and laboratory use EMC requirements Part 1 General requirements EN 61010 1 2011 Safety requirements for electrical measuring control and laboratory instruments EN 60529 2014 Degrees of protection...

Reviews: