VKP
VKP K02/0416
page 5
6. Mechanical
Connection
Before installation:
Make sure that the permitted max. operating pressure and temperature of the
device is not exceeded (see technical data).
These devices are independent of mounting position. A readjustment on
installation position is not necessary. The flow takes place from the float
element to the spring.
Remove all the transportation-safety locks etc. and ensure, that there exist no
packing-material parts inside the unit.
These units may not be installed in the proximity of induction field.
If possible, after mechanical installation, check whether the sealing of
connection-joints/piping is adequate.
(see section on commissioning).
7. Electrical
Connection
Reed-contact, bistable (Option)
Ensure that the electrical power lines are not
active.
Loosen the stopping-screw of plug-cape and
rotate the cap to draw it off from contact-foot.
Assemble the power conductors inside the plug-
cape, as shown in the adjoining figure.
If contact is not yet adjusted, it is desirable to
make the adjustment now (see section on
commissioning).
Place the plug on the contact-foot and secure it
with safety-screws.
Attention! The given electrical values of protective-gas contact
should not be overstepped even briefly. For higher switching
power, we recommend a contact-protected relay (e.g. type MSR
from KOBOLD) or adapt other contact-protection measures.
After connecting the external devices to be used (defined by user) with the limit
contacts, and adjusting the desired switching point, device can be put now into
operation.