Kobold Heinrichs UMC3 Operating Manual Download Page 9

 
 
 

Heinrichs Messtechnik GmbH

 

 

Supplement manual Foundation Fieldbus 

Page

 

9 of 10 

 

 

5.3 

Analog Input Function Block (AI) 

The UMC3-FF contains 4 AI blocks: 
-

 

Flow (mass or volume flow, depending on the unit selected in the transducer block) 

-

 

Density  (in  case  the  density  measurement  is  calibrated  and  switched  on  or  if  a  fixed  density  is 
preset) 

-

 

Temperature 

-

 

Forward  totalizer  (internal  totalizer  of  the  UMC3  transmitter).  This  totalizer  accumulates  mass 
flow or volume flow depending of the totalizer unit selected in the transducer block. 

 
The following parameters have to be set in order to map the measured value at the input of the AI to 
it’s output (default setting when device is shipped) 
 

 

CHANNEL:

 “measured value“ 

 

L_TYPE:

 “Indirect“ 

 

XD-SCALE

 EU_100 corresponds with upper range value 

                            EU_0 = 0 
The “units index“ must be set identical to the unit selected in the transducer block. 
 
If output of AI shall be identically to its input (scaling = 1) following parameters have to be set to: 
 

 

OUT-SCALE equal to XD-SCALE. 

Any unit of OUT value can be selected. There is no conversion between units (e. g. kg -> t) supported 

 

 

LOW  CUT  (low  flow cut off): 

The low flow cutoff is given in % related to the OUT-SCALE. 

When going below this limit the output will be set to zero. In order to activate the low flow cut off 
additionally the parameter IO_OPTS has to be set to “low cutoff“. The setting of the low flow cut 
off  does  not  affect  the  reading  of  the  mass  flow  in  the  local  display.  It  also  does  not  affect  the 
totalizer.  The  Default  setting  is  1%.    Please  regard  that  the  low  flow  cutoff  will  avoid  negative 
readings. 

 
The parameters for monitoring the limits will not be set by default. 
 

PV_FTIME

 (Damping): 

The damping is used to smooth the measured value. Set to 0 seconds by default. The damping value 
set by the local panel is still active even if this parameter is set zero. 

Summary of Contents for Heinrichs UMC3

Page 1: ...nt manual Foundation Fieldbus Rev No 20 01 Page 1 of 10 Operating manual for the electronic transmitter UMC3 FF with Foundation Fieldbus interface UMC3 Supplement to the TM UMC3 TMU UMC3 TMR UMC3 and...

Page 2: ...VALUES _________________________________ 4 3 1 Supply voltage 4 3 2 Basic current 4 3 3 Baud rate 4 3 4 Electromagnetic compatibility EMC 4 3 5 Safety data 4 4 ELECTRICAL CONNECTION __________________...

Page 3: ...media 2 Introduction The Foundation Fieldbus interface of the UMC3 FF offers the possibility to read out the measured values Parameters can be read and changed if needed The interface fulfills the re...

Page 4: ...ting manual UMC3 3 5 Safety data Refer to additional operating manual for explosion proof flow meters FF communications circuit terminals 55 and 56 For connecting a certified FF circuit in accordance...

Page 5: ...inrichs Messtechnik GmbH Supplement manual Foundation Fieldbus Page 5 of 10 4 Electrical connection 4 1 Shielding The shield of the lines at terminals 55 and 56 must be grounded at least at the PLC si...

Page 6: ...or specific parameters as well as the measured values flow density temperature The Analog Input function block AI contains parameters forming the output value limits range low flow cutoff damping valu...

Page 7: ...surement has been calibrated and is switched on or a fixed density is preset Otherwise the output of the AI will be marked as bad Flow unit can be chosen from the following units Mass flow kg s kg min...

Page 8: ...play of the actual sensor amplitude to be used for diagnosis Exciter current display of the actual exciter current to be used for diagnosis Max electronic temperature display of the highest measured t...

Page 9: ...al to the unit selected in the transducer block If output of AI shall be identically to its input scaling 1 following parameters have to be set to OUT SCALE equal to XD SCALE Any unit of OUT value can...

Page 10: ...transducer block will be set Attention XD_SCALE unit in the AI must be set equal via Fieldbus settings Some selectable units of transmitter UMC3 are not available at Foundation Field bus If such a uni...

Reviews: