Kobold Heinrichs TM Supplementary Operating Manual Download Page 15

 
 
 
Heinrichs Messtechnik GmbH 

TM/TMU/TM-SH Supplement Manual 
For Explosion Flow-meters 

Page 15 of 20 

 

5.

 

Maintenance and repair work 

5.1

 

Definition of terms according to IEC 60079-17: 

Maintenance: defines a combination of any actions carried out to retain an item in, or restore it to, conditions in 
which it is able to meet the requirements of the relevant specification and perform its required functions. 
Inspection: defines any action comprising careful scrutiny of an item carried out either without dismantling, or 
with the addition of partial dismantling as required, supplemented by means such as measurement, in order to 
arrive at reliable conclusion as to the condition of an item. 
Visual inspection: defines an inspection which identifies, without the use of access equipment and tools, those 
defects, such as missing bolts, which will be apparent to the eye. 
Close inspection: defines an inspection which encompasses those aspects covered by a visual inspection and, in 
addition, identifies those defects, such as loose bolts, which will be apparent only be the use of access 
equipment, for example steps, where necessary, and tools. 
Detailed inspection: defines an inspection which encompasses those aspects covered by a close inspection and, 
in addition, identifies those defects, such as loose terminations, which will only be apparent by opening the 
enclosure, and/or using, where necessary, tools and test equipment. 

a)

 

Maintenance or replacement work must be carried out by qualified personnel only, i.e. personnel 

qualified according to TRBS 1203 or similar. 

b)

 

Only auxiliary components which comply with all North American requirements, national directives and 

legislations may be used in potentially explosive atmospheres  

c)

 

At the presence of Ex-atmospheres, the equipment must be regularly cleaned. The intervals are to be 

defined by the operator in compliance with the environmental rules valid at the place of operation. 

d)

 

After maintenance and repair works have been performed, all barriers and notices removed for that 

purpose must be returned to their original place. 

e)

 

In the event that faults of the equipment are detected, the equipment is to be removed. The internal 

components cannot be maintained by the customer. The equipment is to be returned to the 
manufacturer for inspection. 

f)

 

Fuses, with the exception of the replaceable mains fuse, may not be replaced by the operator, since 

affected zener-diodes must also be simultaneously replaced. This work requires a follow-up 
adjustment, which can only be carried out at the manufacturer’s factory. 

 

 

Activity 

Visual inspection 

Close inspection  Detailed inspection 

3 month interval 

6 month interval 

12 month interval 

Visual inspection of equipment for 
intactness, removal of dust settlements 

 

 

Check of electrical system for intactness 
and functionality 

 

 

3  Check of entire system 

User's responsibility 

 

Summary of Contents for Heinrichs TM

Page 1: ...AL FOR EXPLOSION PROOF FLOWMETERS EX Supplement MANUAL TM TMU TM SH March 2021 Coriolis mass flow sensors TM TMU TM SH Supplementary Operating Manual for explosion proof flow sensors Please read the i...

Page 2: ...nsor transmitter 8 3 4 EC Type Examination Certificate for the sensors type TM TMU and TM SH 9 3 5 Electrical Parameters 10 3 5 1 Exciter circuit terminals 8 and 9 10 3 5 2 Sensor circuits terminals 1...

Page 3: ...h 2021 or later These instructions are supplementary operating manual for non explosion proof Coriolis flow sensors If you do not have a copy of the latter instructions please request one from Heinric...

Page 4: ...maintenance are to be performed by a technician trained to work with explosion proof devices or by a Heinrichs Messtechnik service technician Warning Any safety relevant maintenance or repairs in term...

Page 5: ...itized using the terms listed below which are defined as follows in regard to the instructions herein and the advisories pertaining to the device itself Warning means that failure to take the prescrib...

Page 6: ...no responsibility for the selection of unsuitably materials Caution To ensure the device performs correctly and safely it must be shipped stored set up mounted operated and maintained correctly 2 Ide...

Page 7: ...rom Heinrichs Messtechnik during your order process Although the appearance of the standard and explosion proof transmitters are often identical and their rating plates contain similar information und...

Page 8: ...rfaces pursuant to EN 1127 1 Explosive atmospheres Explosion prevention and protection paragraphs 5 2 and 6 4 2 3 3 3 Connection remote sensor transmitter A dedicated cable SLI2Y SP CY 5 x 2 x 0 5 mm...

Page 9: ...ficate for the sensors type TM TMU and TM SH The sensors are certified with the following examination certificates CSA North America CSA18CA70171067X Class I Division 1 and 2 Group A B C D Class I Zon...

Page 10: ...Li 4 38 mH 3 5 1 2 For exciter circuit type EC2 For connecting an intrinsically safe circuit with an Ex ia IIC type of protection linear output characteristic and the following maximum values Voltage...

Page 11: ...without 40 45 T6 without 60 60 T5 60 mm 100 80 T4 160 mm 115 80 T4 160 mm 175 80 T3 160 mm 180 80 T2 260 mm 220 80 T2 CAUTION The temperature ranges and classes printed in BOLD and Cursive are NOT ava...

Page 12: ...ables are to be installed in such a way that they are protected against mechanical damage and unduly high temperatures The external diameters of the connecting cables must be compatible with the thick...

Page 13: ...t the equipment is only installed in areas which comply with the approved types of protection and environments e All connected electrical equipment must be suitable for its intended use f The operator...

Page 14: ...t an ambient temperature of less than 20 C or greater 60 C suitable cables cable entries and conduit entries are to be used i The operational wall thickness of the stainless steel flow tubes may be 1...

Page 15: ...nt by opening the enclosure and or using where necessary tools and test equipment a Maintenance or replacement work must be carried out by qualified personnel only i e personnel qualified according to...

Page 16: ...es Such equipment shall only be repaired by expert personnel trained and authorized to do so Damaged threaded or flat joints which may impair the IP protection of the enclosure shall not be repaired o...

Page 17: ...CAN CSA C22 2 No 60079 11 14 Explosive atmospheres Part 11 Equipment protection by intrinsic safety i ANSI ISA 60079 0 2020 Explosive Atmospheres Part 0 Equipment General Requirements ANSI ISA 60079...

Page 18: ...Heinrichs Messtechnik GmbH Page 18 of 20 TM TMU TM SH Supplement Manual For Explosion Flow meters 7 EU Declaration of conformity...

Page 19: ...Heinrichs Messtechnik GmbH TM TMU TM SH Supplement Manual For Explosion Flow meters Page 19 of 20...

Page 20: ...Heinrichs Messtechnik GmbH Page 20 of 20 TM TMU TM SH Supplement Manual For Explosion Flow meters...

Reviews: