ZED-D
page 14
ZED-D K11/0522
GENERAL SETTINGS
Menu Item
Parameter / Function
Explanation / Values / Other
Language
Select menu language
German or English
fUnitFS *
Measuring unit for flow
measurement
mL/s, mL/m, L/s, L/m, L/h, m
3
/m, m
3
/h,
GPM, GPH, UU/s, UU/m, UU/h
fValueFS *
Maximum measuring range value
for flow measurement
Range = 0,00...99,9..._100...9999
fMinVal *
Minimum measuring range value
for flow measurement
Basis is fValueFS and fUnitFS
If the level drops below this, the flow indicator goes to 0.
fPls/rev*
Impulse per sensor wheel
revolution
Number of impulses per revolution of the sensor wheel or the like
Necessary for long-term period averaging if the readings per revolution vary.
The function is switched off when the input value is 1.
fJumpVD *
Flow switch value for attenuation
cut-off
Value in %, basis is fValueFS and fUnitFS.
Attenuation does not function if the switch value is 0%.
fOverflV
Flow overflow value (overflow)
Value in %, basis is fValueFS and fUnitFS.
If exceeded, an M100 report is generated and faded in, alternating
with the flow indicator.
The report is saved and can be reset by briefly pressing the
PGM key.
fFactor
Select pulse ration
Selection of works calibration or user calibration.
(only for devices Model DF-...DLxxx and Model-...GxxR)
UserUnit.
Special volume unit
Customer-specific special unit UU.
The value entered corresponds to the number of litres of the special unit, e.g.
in the case of the unit
Barrel
the factor would for example be 115.6271.
*) Only for ZED devices: Device-specific parameter, is only visible after activation in the
SecCode
menu item in the
SERVICE
menu
group, and can be changed.
Summary of Contents for DF-DL Series
Page 1: ...Operating Instructions for Dosing Electronic Model ZED D or DF DLxxx or Model GxxR...
Page 13: ...ZED D ZED D K11 0522 page 13 7 4 General Settings...
Page 15: ...ZED D ZED D K11 0522 page 15 7 5 Flow and analogue output...
Page 17: ...ZED D ZED D K11 0522 page 17 7 6 Relay output...
Page 19: ...ZED D ZED D K11 0522 page 19 7 7 Dosing...
Page 21: ...ZED D ZED D K11 0522 page 21 7 8 User alignment and Service Settings...