 USER MANUAL CENTRAL HEATING STATION TYPE C32SPV24MEC; C32SPV31MEC

 

 

REV.12.06.2017

 

 

 

      

6 of 18

 

 

7.2.2 Minimum necessary distances/ free spaces for mounting 

 
Both  for  the  mounting/  installation  of  the  central 
heating  stations  and  for later maintenance  operations 
you  will  need  the  following  minimum  distances  (fig. 
1.3), respectively minimum free spaces for mounting: 
– distance to the  lateral: 100 mm 
– distance to the bottom part: 250 mm 
– distance to the upper part: 400 mm 
- distance to front part: 500mm 
 
 

Caution! 
Danger  of  damaging  the  equipment  by 
incorrect setting!  

The  equipment  can  be  mounted  only  on  a  flat,  fixed 
surface. 
 

Note! 
Minimum  necessary  distances/  free  spaces 
for  mounting  are  valid  also  for  mounting 

with/ within pieces of furniture. 
 
 
 
 
 
 

8

 

Installation 

Danger! 

Danger  of  death  by  poisoning  and  explosion  because  of  breeches  in  the  gas  pipes  and  connections  in  case  of 
incorrect installation! 

Installation  and  commissioning  can  be  done  only  by  a  company  authorized  and  agreed  by  KÖBER  SRL-Vaduri 
Branch!

 

 This company will assume responsibility for the correct installation and commissioning. 

8.1

 

Conditions for the installation of the central heating station  

8.1.1

 

Installation directions 

The central heating station will be subject to corrosion from the moment it is filled with water!  
To  receive warranty  during  the  entire warranty  period it is essential  to  take into  consideration  the  following  directions in  order 
not to increase the corrosion! 
- The burning gas must have the sulphur content within the limits of the applicable European standard: it is accepted for a short 
period of time to have a maximum of 150 mg/m3, but the yearly average must be of 30 mg/m3. 
- The burning air must not contain chlorine, ammonia, alkaline agents, halogenated hydrocarbs, freon, plaster particles, lints, 
dirt or dust; 
- Installation  of  the  central  heating  station in  the proximity  of a  swimming pool, washing  machine  or cleaner  can  result in  the 
contamination of the burning air with these compounds.  
-  Water pH must be within the following limits: 7,5<pH<9,5 

- It is recommended to check the water and thermal agent pH frequently and if the value does not fall within the limits provided 
by the manufacturer, it will be treated again.  

-  Water  asperity  must  be  within  the  limits  5°F  <TH  <15°F  (5°F  (French  degrees),  equivalent  to  50  mg  CaCO

3

  or  an  equivalent 

quantity of other Ca and Mg salts). 
- It is recommended to have repeated station startup cycles with the fuel tap off in order to air the installation. 
- If  the  central  heating  station is  not  used  for a long  period  of  time  during  the  cold  season,  full emptying  of  the installation is 

recommended to prevent damage caused by freezing.  

8.1.2

 

Protection of the station in order to keep the warranty  

Before and  during installation, the  central heating  station  must  be  kept  away  from impurities:  construction  dust,  sand,  copper 
dust, fats etc as well as welding splashes, scoria. In any of theses cases, the installation must be washed with clean water mixed 
with a highly concentrated cleaning agent.  
 
Genereally, 

in  order  to  keep  the warranty  it  is  necessary

  to  apply  any  neccesary  treatment  to  prevent  the  contamination  of 

water with the following: 

 

Black mud (magnetite - Fe3O4) formed as a result of the continuous electrolyte corrosion occurring in any installation 

which is not protected with an inhibitor.  

 

Red mud (rust - Fe2O3) produced during oxidation.  

 

Calcarous deposits produced especially on the hottest areas of the central heating station.  

A combination of these three factors mentioned above causes the majority of the problems occurring with heating systems.  

Caution! 
The presence of these substances (black mud/ red mud/ calcarous deposits) means that the standard measures to 
prevent problems of the heating system were not observed. This is one of the causes resulting in losing warranty!  

Fig. 1.3 

Summary of Contents for C32SPV24MEC

Page 1: ...C C32SPV31MEC Image for presentation only Product may look slightly different depending on the area and the purchase period KÖBER SRL no 25 Vaduri Alexandru cel Bun Commune Neamt 617511 Romania Tel 40 233 24 17 46 233 24 19 33 Fax 40 233 24 19 29 www motan ro ...

Page 2: ... 2 3 Graphic context Stand by 10 9 2 4 Graphic context error state 11 9 2 5 Graphic context waiting state 11 9 2 6 Graphic context functioning state 11 9 2 7 Graphic context adjustment of functioning parameters 11 9 2 8 Graphic context Service submenu 12 9 3 Central heating station startup 12 9 4 Functioning as waste hot water station WHW 12 9 5 Functioning as heating station HS 12 9 6 Preset func...

Page 3: ...le with limited psychological and sensitive capacities including children or by people with no experience or and no knowledge The station provides both heating in closed circuit central heating installations as well as hot water Use for other purposes or for additional purposes other than stipulated is considered inappropriate use The manufacturer is not responsible for possible damage resulting f...

Page 4: ...ure min max on thermal circuit 0 5 3 5 bar Maximum pressure on DHW circuit 8 bar Temperature on thermal circuit 30 80 C Temperature on the floor heating system circuit 15 45 C Temperature on domestic hot water circuit 35 55 C Hot water flow t 30 C 10 l min 12 l min Electric characteristics Input 230VAC 50 Hz Rated power EEI pump 0 2 70 W Construction characteristics Height 700 mm Width 436 mm Dept...

Page 5: ... 60 humidity between 20 30 C in order to prevent the damaging of electronic components Caution The burning air of the station must not contain substances such as flourine vapours chlorine sulphur dissolvants colorants adhesives or gasoline These substances can lead in time to the corrosion of the equipment and air gas incoming outgoing pipes Legend A Thermal input connector B Hot water output conn...

Page 6: ...n of the central heating station in the proximity of a swimming pool washing machine or cleaner can result in the contamination of the burning air with these compounds Water pH must be within the following limits 7 5 pH 9 5 It is recommended to check the water and thermal agent pH frequently and if the value does not fall within the limits provided by the manufacturer it will be treated again Wate...

Page 7: ...return of the thermal circuit installation When installing connecting pipes it is essential for these not to be tensed to avoid creating areas of leakage Maximum working pressure allowed is 3bar Recommended working pressure is 1 5 bar Caution It is forbidden to use the central heating station without thermal agent or partilally filled danger of explosion It is forbidden to use the central heating ...

Page 8: ... Electric powering of the central heating station will be executed from a separate circuit provided with differential protection fuses of 30 mA External connections must comply with applicable norms Connection to the electric grid of the building must allow the entire electric insulataion of the central heating station for situations when interventions are required Grid connection is done taking i...

Page 9: ...of the main switch of the station Incorrect airing of the installation can cause damage of the main heating switch Note Recommended pressure on the thermal circuit is 1 5 bars Emptying the central heating station Emptying of the station implies the following turn off the station by pressing Power si switch off the electric power close the gas tap close the thermal tap and the cold water input tap ...

Page 10: ...er in the installation submenu Used to decrease the set temperature on hot water circuit or the value parameter in the installation submenu Used to switch the station on off Used to reset the electronic control board from an error state Used to change the functioning mode winter summer Used to activate deactivate the light on the display Description of graphic symbols in the LCD display Descriptio...

Page 11: ...on is 1 4 bar working mode is summer and the temperature in the installation is 17 C 9 2 6 Graphic context functioning state This state is associated with the presence of flame or the functioning of the circulation pump of the station In this state all the activating state elements of the central heating station are active and the burning request is accepted The display shows the delivered instant...

Page 12: ...est has priority over the heating request in the winter mode The station can function as instant WHW or as accumulation boiler WHW the boiler is functioning of the station as an accumulation boiler WHW station please contact an authorised service company In intant regime the minimum flow of hot water detected by the station is 2 4 l min For confort in using the station as a WHW station we recommen...

Page 13: ...e detection Manually resettable by pressing RESET E25 YES BCU malfunction Manually resettable by pressing RESET E30 YES Malfunctioning burnt gases sensor Manually resettable by pressing RESET E31 NO Malfunctioning thermal input sensor Manually resettable by pressing RESET when the cause disappears E32 NO Malfunctioning thermal output sensor Manually resettable by pressing RESET when the cause disa...

Page 14: ...ed table 2 by which the user signs that they are aware of the correct way of using the central heating station This statement is also signed by the authorized person who commissioned the central heating station The authorised person who commissions the station has the right to refuse to sign the station commissioning statement if they notice defects of the local connecting installations and will n...

Page 15: ...ON TYPE C32SPV24MEC C32SPV31MEC REV 12 06 2017 15 of 18 11 Drawings necessary for mounting and installation 11 1 Types of configurations for mounting the flue kit 1 m max Min 3 2 Min 1 5 m min min1m 1 m max Min 3 2 Min 1 5 m min min1m ...

Page 16: ... Pump error codes If the pump has detecte one or more errors the bi colour LED 1 changes from green to red When an error is active LEDs indicate the type of error as presented in table 7 If more alarms are active at the same time LEDs show the rror with the highest priority Tab 7 Pump error codes 11 3 Hydraulic characteristic of non ER P pump Q PUMP FLOW mc h Display Meaning Pump action Repair 1 L...

Page 17: ...4MEC C32SPV31MEC REV 12 06 2017 17 of 18 11 4 Functioning schemes covered by warranty 11 4 1 Central heating with radiators and instant preparation of domestic hot water 11 4 2 Underfloor central heating and instant preparation of domestic hot water ...

Page 18: ...EC C32SPV31MEC REV 12 06 2017 18 of 18 11 4 3 Central heating with radiators and accumulated preparation of domestic hot water accummulation boiler 11 4 4 Underfloor central heating and accumulated preparation of domestic hot water accummulation boiler ...