8
4 Commissioning/Operation
4.1 The initial start-up
The initial start-up is carried out either by KÖB
Holzfeuerungen GmbH or a competent individual
named by it.
Be absolutely sure to follow the instructions in
the Assembly and Installation Instructions. No
guarantee may be claimed for damages in
cases of initial start-ups carried out improp-
erly at one's own initiative.
First check:
-
Is there enough water in the heating system?
-
Has the heating system been bled of air?
-
Are the slide valves open for the heating-
system's forward and reverse flow?
-
Can enough fresh air get into the heating
room?
-
Empty ash bin.
-
Are the doors and lids on the burner all closed
leak-tight?
4.2 Operation
4.2.1 Heating up
-
Press the F1 key "PYROT Wood". The loader
modules will be switched on in the appropriate
order. When there is enough fuel in the com-
bustion chamber, the entire loader system
switches off.
-
The automatic ignition then takes place. The
ignition process stops as soon as the fire is
started.
4.2.2 Operation
-
The material is supplied depending on the light
barriers in the metering container and in the
combustion chamber, allowing for the residual
oxygen.
-
The primary and secondary air vents change
their positions depending on the exhaust gas
temperature and residual oxygen.
-
Using the setting "Storage Management, Tem-
perature, Storage, Average", it is possible to
keep the facility in continuous high-
performance operation for as long as possible
– with fewer ignitions, better efficiency and lo-
wer emissions.
(Only possible with accumulator option)
-
When the boiler temperature set is reached,
the facility switches to "Run Auger Empty".
When the feed auger has been run empty, and
the exhaust gas temperature is less than 90°C,
the exhaust gas fan switches off and the air
vents close.
-
When the "System Temperature Setting" is
fallen short of, the facility is automatically star-
ted back up.
4.2.3 Switching off
-
Press the F1 key "PYROT Wood". As feed-
back to this, "Run Auger Empty" will appear on
the control panel.
CAUTION: Do NOT use the master button to
switch off (DANGER OF BACK BURN) !!!
Summary of Contents for KOB PYROT SERIES
Page 1: ...Operation and Maintenance Instructions PYROT 100 to 540 ID 106811 H English ...
Page 29: ...Leerseite für Notizen Blank page for notes Page en blanc pour des notationes ...
Page 30: ...Leerseite für Notizen Blank page for notes Page en blanc pour des notationes ...
Page 31: ...Leerseite für Notizen Blank page for notes Page en blanc pour des notationes ...