12
6.3.2 The F4 KEY: "PYROT Loader System"
(mask number) parameter (factory setting)
(01) Cleaning (NO):
This activates the cleaning function. Exhaust fan
at starting speed, and moving grate on.
(05) Moving grate, pause (60 s):
Cycle switching for the moving grate (adjustable
pause time, impulse fixed, 2 seconds).
(07) Metering container,empty running time
(5s):
Running time for feed auger with the light barrier
for the feed auger clear
Æ
prompt for material
(08) Conveyor Device 1/Delay (3 s):
Delay before connecting Conveyor System 1
(e.g. rotary valve, conveyor auger, etc.)
(09) Conveyor System 1, after-running (0 s):
After-running of Conveyor System 1
(e.g. pneumatic conveyor, etc.)
(10-37) Conveyor Systems 2-15:
Delay before connecting or after-running of Con-
veyor Systems 2 to 15
(38) Extraction System 1/Delay (3 s):
Delay before connecting Conveyor System 1
(e.g. spring-operated extraction system, inclined
extraction system, etc.)
(39) Extraction System 1/Impulse (5 s):
Impulse for the cycle switching for Extraction Sys-
tem 1 (e.g. spring-operated extraction system, in-
clined extraction system, etc.)
(40) Extraction System 1, Pause (0 s):
Pause in the cycle switching for Extraction Sys-
tem 1 (e.g. spring-operated extraction system, in-
clined extraction system, etc.)
(41) Extraction System 2/Delay (3 s):
Delay before connecting Conveyor System 2
(e.g. spring-operated extraction system, inclined
extraction system, etc.)
(42) Extraction System 2/Impulse (5 s):
Impulse for the cycle switching for Extraction Sys-
tem 2 (e.g. spring-operated extraction system, in-
clined extraction system, etc.)
(43) Extraction System 2, Pause (0 s):
Pause in the cycle switching for Extraction Sys-
tem 2
(e.g. spring-operated extraction system, inclined
extraction system, etc.)
(44)Extraction System 1/Hydraulics/Delay
(5 s):
Delay before connecting hydraulic drive for
Extraction System 1
(45) Extraction System 2/Hydraulics/Delay
(5 s):
Delay before connecting hydraulic drive for
Extraction System 2
(50) Silo filling:
Start silo filling (only possible
when the facility is not in operation and has
cooled off).
Summary of Contents for KOB PYROT SERIES
Page 1: ...Operation and Maintenance Instructions PYROT 100 to 540 ID 106811 H English ...
Page 29: ...Leerseite für Notizen Blank page for notes Page en blanc pour des notationes ...
Page 30: ...Leerseite für Notizen Blank page for notes Page en blanc pour des notationes ...
Page 31: ...Leerseite für Notizen Blank page for notes Page en blanc pour des notationes ...